York R-410A User Manual
Page 85
251933-YTG-J-1009
Johnson Controls Unitary Products
85
060
(5.0)
208-3-60 17.6 123.0
27.5
2.3
8.2
10.0
None
-
-
-
42.5
60
E05
4.0
1
11.1
42.5
60
E07
5.6
1
15.5
42.5
60
E10
8.0
1
22.2
50.5
60
E15
11.9
2
33.0
64.0
70
E20
15.9
2
44.1
77.9
80
E30
22.2
2
61.6
99.8
100
230-3-60 17.6 123.0
27.5
2.3
8.2
10.0
None
-
-
-
42.5
60
E05
5.3
1
13.3
42.5
60
E07
7.5
1
18.8
45.3
60
E10
10.6
1
26.6
54.6
60
E15
15.9
2
39.9
70.6
80
E20
21.2
2
53.2
86.5
90
E30
29.6
2
74.3
111.8
125
460-3-60
9.6
70.0
15.0
1.3
4.1
5.0
None
-
-
-
22.4
30
E07
6.8
1
8.5
22.4
30
E10
10.1
1
12.7
26.6
30
E15
13.6
2
17.1
31.8
35
E20
19.5
2
24.5
40.7
45
E30
28.8
2
36.1
54.7
60
575-3-60
7.5
53.0
11.7
1.3
3.6
4.0
None
-
-
-
18.0
25
E10
10.6
1
10.6
22.2
25
E15
15.9
1
16.0
28.6
30
E20
21.2
2
21.3
35.0
35
E30
30.4
2
30.5
46.1
50
1. Minimum Circuit Ampacity.
2. Dual Element, Time Delay Type.
3. HACR type per NEC.
ZR036-060 (Belt Drive High Static) (Continued)
Size
(Tons)
Volt
Compressors
(each)
OD Fan
Motors
(each)
Supply
Blower
Motor
Pwr
Conv
Outlet
Electric Heat Option
MCA
1
(Amps)
Max Fuse
2
/
Breaker
3
Size
(Amps)
RLA
LRA
MCC
FLA
FLA
FLA
Model
kW
Stages
Amps