Typical field power and control wiring, Cooling only (24 volt thermostat), Cooling / heating (24 volt thermostat) – York R-410A User Manual

Page 94

Advertising
background image

251933-YTG-J-1009

94

Johnson Controls Unitary Products

Typical Field Power and Control Wiring

REFER TO THE ELECTRICAL DATA
TABLES TO SIZE THE DISCONNECT
SWITCH, OVERCURRENT PROTEC-
TION AND WIRING.

RC

RH

Y1

Y2

W1

W2

G

LED 1

LED 2

COM

A1

A2

T

T

B

R

Y1

Y2

G

C

X

OCC

W2

W1

THERMOSTAT

1

TERMINALS

UNIT TERMINAL

STRIP TB1

24 VOLT

TRANSFORMER

TO REMOTE SENSOR

IF USED

NOT
USED

ADD

JUMPER

ADD

JUMPER

4

4

3

2

1

ELECTRONIC PROGRAMMABLE THERMOSTAT TYPICAL.

2

SECOND STAGE COOLING IS NOT REQUIRED ON UNITS LESS ECONOMIZER.

3

SECOND STAGE HEATING IS ONLY REQUIRED ON UNITS WITH A TWO STAGE

ELECTRIC HEATER OR 2 STAGE GAS HEAT.

4

REMOVE JUMPER J2 FROM TERMINALS 4 AND 9 ON JUMPER PLUG CONNECTOR
P6 ON UNITS WITH ECONOMIZER. TERMINALS A1 AND A2 PROVIDE A RELAY
OUT-PUT TO CLOSE THE OUTDOOR ECONOMIZER DAMPERS WHEN THE
THERMOSTAT SWITCHES TO THE SET-BACK POSITION.

COOLING / HEATING (ELECTRONIC THERMOSTAT)

MULTI STAGE

RH

RC

Y

W

G

R

Y1

W1

C

G

ADD

JUMPER

THERMOSTAT

1

TERMINALS

UNIT TERMINAL

STRIP TB1

24 VOLT

TRANSFORMER

1

ELECTRONIC PROGRAMMABLE THERMOSTAT TYPICAL. TO CONTROL THE
ECONOMIZER ON SECOND STAGE COOLING, USE A 2 STAGE COOL AND
HEAT THERMOSTAT.

COOLING / HEATING (ELECTRONIC THERMOSTAT)

SINGLE STAGE

RV

YC

GF

R

Y1

C

Y2

THERMOSTAT

1

TERMINALS

UNIT TERMINAL

STRIP TB1

24 VOLT

TRANSFORMER

1

24 VOLT THERMOSTAT. TO CONTROL THE ECONOMIZER ON SECOND
STAGE COOLING, USE A 2 STAGE COOLING THERMOSTAT.

G

COOLING ONLY (24 VOLT THERMOSTAT)

RC

Y

R

Y1

Y2

W1

W

W2

G

C

G

RH

THERMOSTAT

TERMINALS

UNIT TERMINAL

STRIP TB1

24 VOLT

TRANSFORMER

ADD

JUMPER

1

24 VOLT THERMOSTAT. TO CONTROL THE ECONOMIZER ON THE SECOND
STAGE COOLING OR TO HAVE AN ELECTRIC HEAT ACCESSORY WITH TWO
STAGES OF HEAT, USE A 2 STAGE COOL AND HEAT THERMOSTAT.

1

COOLING / HEATING (24 VOLT THERMOSTAT)

TYPICAL POWER WIRING

TYPICAL COOL/HEAT CONTROL WIRING

Advertising