Introduction

1–6

975-0288-01-01

Standby Mode

In the Standby Mode, the Charger is OFF but monitors the battery
voltage. If battery voltage drops below

12.5

Vdc, the unit will start a new

Bulk stage.

The PowerHub 1800 will reset to the default setting of 40 A whenever
one of the following occurs.

1. The unit is turned OFF by the ON/OFF Button.

2. All DC input sources (solar panels or wind generators) are removed

and utility AC is not available.

Figure 1-3 Three-Stage Charging Process

Voltage

Bulk

Stage

Absorption

Stage

Float Stage

Standby

(Stop Mode)

Current

Maximum

Charge

Amps

Setting

14.2 Vdc

13.7 Vdc

40 A or

10 A

4 A

12.5 Vdc

Time

4 A

12.5 Vdc

Time

6 A

If the current rises to 6A

during the Float period, the

Charger will start the whole

cycle back at the Bulk Stage.

4 hours

(Maximum)

If the voltage drops to 12.5 Vdc

while in Standby, the Charger

will start a new Bulk Stage.

8 hours

4 hours

(Maximum)

8 hours

Current

40 A or

10 A

Maximum

Charge

Amps

Setting