Current – Xantrex Technology PH1800 User Manual

Page 52

Advertising
background image

Specifications

A–4

975-0288-01-01

Float Stage

In the Float stage, the constant voltage mode limited to 13.7 Vdc. An 8-
hour timer is started at this point.

If, during the 8-hour timer, the current rises to 6 A, the unit transitions
back to the Bulk Stage and starts over.

If the unit stays at 4A or less for the 8 hour timer, it will transition to
Standby Mode.

Standby Mode

In the Standby Mode, the Charger is OFF but monitors the battery
voltage. If battery voltage drops below

12.5

Vdc, the unit will start a new

Bulk stage.

Figure A-1 Three-Stage Charging Process

Voltage

Bulk

Stage

Absorption

Stage

Float Stage

Standby

(Stop Mode)

Current

Maximum

Charge

Amps

Setting

14.2 Vdc

13.7 Vdc

40 A or

10 A

4 A

12.5 Vdc

Time

4 A

12.5 Vdc

Time

6 A

If the current rises to 6A

during the Float period, the

Charger will start the whole

cycle back at the Bulk Stage.

4 hours

(Maximum)

If the voltage drops to 12.5 Vdc

while in Standby, the Charger

will start a new Bulk Stage.

8 hours

4 hours

(Maximum)

8 hours

Current

40 A or

10 A

Maximum

Charge

Amps

Setting