Inverter Control Panel

975-0288-01-01

2–5

Solar LED

When the Select Button is pressed again within 10 seconds and the Solar
LED is illuminated, the Solar Input wattage levels are displayed in
kilowatts. These values are the inputs on the 32 A DC input terminals.

AC LED

If the unit is in Bypass Mode, when the Select Button is pressed again
within 10 seconds and the AC LED is illuminated, the battery charger
power level is displayed in kilowatts.

Output LEDs

Net Power LED

By default the Net Power LED represents the difference between the
input and the output power levels. This value is shown on startup and will
return to this display if the Select button is not pressed for 10 seconds.

When using the Select Button to cycle through the displays and the Net
Power LED is illuminated, the power level displayed will depend on
whether the unit is in Bypass Mode or Inverter Mode.

In Bypass Mode, the value displayed represents the power, in kilowatts,
that is available to charge the battery and to power the loads. This will be
a positive number.

In Inverter Mode, this value displayed represents the total amount of
power in kilowatts that is being drawn from the battery bank (negative
numbers) or is available to charge the battery by the DC source while the
inverter is running (positive numbers).

Battery LED

When the Select Button is pressed again within 10 seconds and the
Battery Level LED is illuminated, the battery voltage level is displayed in
DC volts. It will also show “FUL” when the battery is charged through the
AC charger and reaches float and standby mode.

Output LED

When the Select Button is pressed again within 10 seconds and the
Inverter LED is illuminated, the Inverter Output power is displayed in
kilowatts. This only displays if the unit is in Invert Mode.

Selecting Charger Settings

Charger
Settings

Pressing and holding the Select Button for 3-5 seconds will change the
display to show the AC charger current setting and the AC LED will
flash.

See “Battery Charger Features” on page 1–5 for more information
regarding setting parameters. See “Changing Charging Settings” on
page 2–9 for instructions on changing this setting.