PNEG-900 Series 2000 Autoflow Fan/Heater and Control Installation Instructions

33

Natural Gas (NG)

This dryer is designed to operate on natural gas. Natural gas units have a larger orifice to accommodate
lower pressures sometimes found with natural gas and do not have vaporizer coils like liquid propane
units. A regulated pressure of 10 PSI minimum, 30 PSI maximum must be provided at the field connection
point on the fan/heater unit, with gas available in sufficient volume to maintain the operating pressure.

See the

below

“Fuel Systems and Recommendations Chart” for natural gas (NG) to determine the correct

size line to run to the dryer. Have a qualified gas service person inspect the installation to be sure
everything is installed according to local codes and ordinances.

After installation is complete, check all connections for leaks with liquid detergent or comparable. Wear
rubber gloves and eye protection.

Figure 3W NG Line Field Connection

Fuel System Specifications and Recommendations Natural Gas (NG)

Dryer

Fan Size

Dryer

Horsepower

Maximum Heat

Capacity BTU

per Hour

Maximum Fuel

Flow Cubic Ft.

per Hour

Minimum

Line Size

Orifice Size

Minimum

Operating

Pressure

Maximum

Operating

Pressure

36"

15

5 Million

5280

2"

1/2"

1 lb.

7 lbs.

40"

15

5.5 Million

5965

2"

17/32"

1 lb.

7 lbs.

42"

30

9 Million

9536

2"

43/64"

1 lb.

7 lbs.

42"

40

9.5 Million

10445

2"

45/64"

1 lb.

7 lbs.

WARNING

Do not use flame for leak testing.