4. Electrical Power Supply

48

PNEG-900 Series 2000 Autoflow Fan/Heater and Control Installation Instructions

Master to Slave Interconnect

A slave fan/heater unit can be added to operate in unison with the master fan/heater unit. The interconnect
between the master and slave fan/heater units remains the same regardless of the type or presence of a
control center. To wire a slave fan/heater unit to a master fan/heater unit do the following:

NOTE: Do NOT use solid wire for interconnection.

1. Run four (4) 16 gauge MTW type wires from the master fan/heater unit to the slave fan/heater unit.

2. Connect the wires as shown in

Figure 4L

.

NOTE: A shielded 16 gauge cable is recommended for use on the network connections. The network

connections for this configuration are attached to terminal #8 and terminal #9 in the master unit and
terminal #3 and terminal #4 in the slave unit. Ground each end of the shielded cable to the housing.
A shielded 16 gauge 2 wire cable can be purchased from GSI. Part #WR-16/2S.

Slave #1 Fan and Heater Dip Switch Setting: #2 - “OFF”/All Others - “ON”

Figure 4L Wiring for a slave fan/heater unit to a master fan/heater unit.