Network autoflow tips, 2003 top dry service school – Grain Systems PNEG-1314 User Manual

Page 30

Advertising
background image

2003 Top Dry Service School

3 0

Network Autoflow Tips

Present Version Numbers: Display  2.15

Heater  1.09 IO 1.07

Note: Display version

2.14 and 2.15 will not work with Heater version 1.10 you must use version

1.09.

Important Software and Troubleshooting tips

Special Wire Terminals

- The third unused terminal on any network connector is a 12 V ground

for use with a tester.

1. When ever you install a new display board. After you flash the software in and restart you may see an
ERROR Message with some garbage characters or a negative number for temperature such as -2785
degrees. Do a Hard Boot by holding the Reset key and turning the power on to correct this stuck register
value.
2. Always do a Hard Boot after installing a new Display board.
3. If you have a blank or all black screen see the Contrast Adjustment in Tip #1
4.

Also when flashing new software to the IO Board turn off the load auger breaker(s).

Due to a design

characteristic the load auger(s) will run whenever the IO board is being flashed.
5. If the Fan motors run, but the augers and aeration fan do not, make sure the 110 volt breaker on the IO
board is turned on.
6. The

newest Display boards (5/1/02)can now be used on either a Topdry or Portable Dryer.

In the past a

Dryer Display board
had to have wires soldered in place for the Meter Roll Speed Pot and they can also be used on either a
Top Dry or Portable
Dryer.

The past Top Dry Display board without these wires could be used on a Top Dry only.

The

newest boards now have a
six pin connector that the Dryer Meter Roll Speed Pot is connected to.
7.

If you get a plenum High Limit Error on startup with a new system or after installing new software on a

Two Fan Top Dry
check to see if a jumper from J7-3 to J7-15 fixes it.

8. Grain Temperature Sensors are 10 ½” from the top of the floor rib. Older Top Drys were 14” from
the flat of the floor.

Version Specific changes

Version 2.15 See separate Sheet at page 3 for substantial changes in operation.
Version 2.14
1.

Extended Setup is now accessed by holding down the Modify key while

powering up

2. Low limits were set. 150 degrees for Grain High limit and 200 degrees for Plenum

High limit.
Version 2.11 1. When grain reaches the Storage Chamber Rotary Switch a "Cool Down Mode"
will be entered.
The fan will run and cool the grain for 10 minutes before shutting down due to a Storage Chamber
Full error.
When grain leaves the Wet Supply Rotary Switch. The fan will cool for 10 minutes before giving
out of grain error .
When the Dry & Hold switch is placed in the "On" position the fan will Cool for 20 minutes before
stopping.
Version 2.06

Stopped the ability to change the grain setpoint from heaters

.

Version 2.04

Made all air switches active once again. New venturi Air Switches must be

present

on each fan where more then one fan is in use. Single Fan systems can continue to use the

existing Plenum Air Switch.

Version 2.03 The user can no longer go into Extended Set Up while the dryer is running.
Version 1.02 Release Date Jan of 98 the

Bin High Limit rotary switch is now monitored in both states

to insure that a switch
failure has not taken place. If both switches are in the same state a switch failure is reported.