7.3.2 Intermediate load limits connections

One or two “normally closed” contact should be connected to the multi-functional inputs. The contacts
can either be manual switches, or automatically actuated according to the position of the crane.

The intermediate load function operates according to the following logic:

MFI1
oper.

MFI2
Oper

MFI1
status

MFI2
status

Active load limit

NU

NU

-

-

Normal Overload limit

IntL

NU

ON

-

Normal Overload limit

IntL

NU

OFF

-

MFI1 load limit. The parameter 4-1-2

NU

IntL

-

ON

Normal Overload limit

NU

IntL

-

OFF

MFI2 load limit, The parameter 4-2-2

IntL

IntL

ON

ON

Normal Overload limit

IntL

IntL

ON

OFF

MFI1 load limit. The parameter 4-1-2

IntL

IntL

OFF

ON

MFI2 load limit. The parameter 4-2-2

IntL

IntL

OFF

OFF

MFI1+2 load limit. The parameter 4-2-3

The hoist-monitoring unit will prevent the hoisting motion when the measured load exceeds 110%
of the intermediate load for a period of time. The overload protection is reset when the measured
load decreases to 80% of the intermediate load.

Connections if this function is used to do a load limited area

7.4 Run time and start counter for trolley and bridge

In addition to the hoist run-time and starts counter, the hoist-monitoring unit can be programmed to count
the total run-time and starts of either the trolley and/or bridge travel motion. When this option is activated,
a complete overview of the usage of the crane is recorded.