9.3.2.5 Second overload limit ”2OLL”

•

When MFI1 input is activated then the hoist can lift over the nominal load (1.00 – 1.30 x nom.).

•

Check by parameter 1-2-14, that MFI1 status bit is 1 when lifted in the area where need lift more than
nominal load.

9.3.2.6

Levelling function ”Level”

•

Drive one of the hooks higher upwards than the other(s)

•

Select common hoisting with the selector switch on the control station.

•

Drive all hooks upwards to the upper limit.

•

When the highest hook stops, the other(s) should continue until the hooks are balanced

9.3.2.7 Bridge intermediate load limit ”CIntL”

•

Bridge intermediate load limit is activated when input is not active.

•

When actual load value exceeds a limit and the input is not active the unit works similarly as in
overload situation.

•

Check bridge intermediate load limit value by parameter 4-2-5.

•

Check that the hoist control device sees then the input status by parameter 1-2-14. MFI1 input’s
status bit is second bit from the right (XXX1X)

9.3.2.8 By-pass CAN-bus ”CAN”

•

The control unit must have a button or a switch for this functions.

•

CAN bus by-pass function is activated when input is active.

•

Test that the hoist control device sees the input status by parameter 1-2-14.

9.3.3 Functional free relay output ROUT

•

Check the relay operation by parameter 4-3-1

•

Check the operation logic of the relay by parameter 4-3-2. Normal operation is as described below.

9.3.3.1 Overload ”OL”

•

Contact closed when overload is detected.

•

Check that the relay works.

9.3.3.2 Load limit function ”LoadX”

•

Contact closed when the load exceeds the limit “X”, where the limit is determined by parameter 4-3-3

•

Check the limit value from the parameter 4-3-3

•

Check that the relay works.

9.3.3.3 Fault- and warning -state supervision ”OK”

•

Contact closed in normal operation

•

Contact blinks when the unit shifts to “warning state”

•

Contact opens when the unit shifts to “fault state

•

Check that the relay works.

9.3.3.4 Fault supervision ”Ready”

•

Contact closed in normal operation

•

Contact opens when the unit shifts to “fault state”

•

Check that the relay works.