5 analogue output, 1 analogue output parameters – R&M Materials Handling HOIST MONITORS User Manual

Page 37

Advertising
background image

R&M Materials Handling, Inc.
4501 Gateway Boulevard
Springfield, Ohio 45502
P.: (937) 328-5100
FAX: (937) 325-5319

37/105

R&M Materials Handling, Inc. reserves the right to alter or amend the above information without notice.

7.4.1 Run time and start counter for trolley and bridge parameters

Parameter

Value

Description

Note

4-1 MFI1

Accessible with password 4: 8124

4-1-1
MFI1 oper.

ST/RT

Start counter and run-time counter

Counts the amount of times the MFI1 input becomes active (starts)
and the total time the MFI1 input is active (run-time)

Parameter

Value

Description

Note

4-2 MFI2

Accessible with password 4: 8124

4-2-1
MFI2 oper.

ST/RT

Start counter and run-time counter

Counts the amount of times the MFI2 input becomes active (starts)
and the total time the MFI2 input is active (run-time)

Parameter

Value

Description

Note

1

Monitor 1

Accessible with password 1

1-1-7
MFI1 RT

“n”h

Displays the total time MFI1 has been active
(run-time counter)

Read only value

1-1-8
MFI1 ST

“n”

Displays the amount of times MFI1 has been
activated (starts counter)

Read only value

1-1-9
MFI2 RT

“n”h

Displays the total time MFI2 has been active
(run-time counter)

Read only value

1-1-10
MFI2 ST

“n”

Displays the amount of times MFI1 has been
activated (starts counter)

Read only value

7.4.2 Run time and start counter for trolley and bridge connections

A normally open contact of the trolley and/or bridge travel brake contactor is connected to the MFI1
and/or MFI2 input. Without a brake contactor the control command can be duplicated to the MFI1 and/or
MFI2 input.

7.5 Analogue output

The hoist-monitoring unit has one analogue output, which can be used for e.g. a load display or a relay
board that provides certain relay operations according to the load value. The analogue output has a
voltage range of 0…10 VDC. The analogue output can be programmed to represent either the actual
load (or sum load in multi-hoisting), the tared load (or summed tare load in multi-hoisting) or the actual
load of the connected hoist.

7.5.1 Analogue output parameters

Parameter

Value

Description

Note

4-6 AOUT

Analogue output parameters

Accessible with password 4: 8124

4-6-1
AOUT oper.

Act
Tare
Solo

Actual load’s values in the output
Tared Load’s values in the output
Solo hoist’s load values in the output,
Parameter 1-2-1

Actual sum load in multi hoisting application.
Tared sum load in multi hoisting application.
Tare function is made for each hoist individual; means tare
command is not transferred to other units via CAN bus. Same
function as in the display.

4-6-2
Zero load

2.00V

Analogue output voltage with zero load

Adjustable according to the needed voltage of the connected device
when required. *1)

4-6-3
Nom. Load

8.00V

Analogue output voltage with rated load. Refer to
parameter 6-4 for the rated load in single hoist
operation
Refer to parameter 4-11-4 for the rated load in
multi-hoist applications

Adjustable according to the needed voltage of the connected device
when required. *2)

*1) The zero load voltage should be higher than 0.00V in order to achieve “broken wire protection”
*2) The rated load voltage should be less than 10.0V in order to allow overload indication.

Reliable ranges are from 2V to 8V with large display and from 1V to 9V with other devices e.g. PLC
equipments.

Advertising