R&M Materials Handling HOIST MONITORS User Manual

Page 72

Advertising
background image

R&M Materials Handling, Inc.
4501 Gateway Boulevard
Springfield, Ohio 45502
P.: (937) 328-5100
FAX: (937) 325-5319

72/105

R&M Materials Handling, Inc. reserves the right to alter or amend the above information without notice.

14.1.8 Fault Sensor ch.

F_SCh

Measurement signal out of acceptable range
•

Measure the voltage across terminals 26 (I1-A) and 30 (0V). Voltage should be between 0.5...9.5VDC
(low at zero-load; high when load attached to the hook)

•

Check the parameter 1-2-10 value

-

The parameter 1-2-10 value should be nearly the same as measured, ±1 VDC. If the parameter’s value is
different than measured value then it is possible that input is broken.

-

If the parameter 1-2-10 value is ~9.8V

•

The signal wire hasn’t been connected to the Analog input 1 (the terminal 26)

•

The neutral wire is broken between the unit and the sensor

•

Check the connections between the amplifier and strain gauge sensor.

•

If the parameter 1-2-10 value is less than ~1V

-

Measure the voltage across terminal 25 (10V) and 30 (0V). Voltage should be about 10….12VDC

-

The power signal wire (10V) is broken between the terminal 25 and the sensor

-

The strain gauge sensor is not connected to the amplifier.

-

Check the connections between the amplifier and strain gauge sensor.

When the load sensor calibration is done in way, that the zero-load voltage is less than
1.0VDC, the fault only occurs when the signal becomes greater than 9.5VDC.

14.1.9 Fault Curr.meas.

F_Ain

Measurement signal out of acceptable range (only two step control)
•

Measure the voltage across terminals 29 (IB) and 30 (0V). Voltage should be about 5VDC

•

Measure the voltage across terminals 27 (I2-A) and 29 during hoisting and lowering, low and fast
speed. Voltage should be between 0.5…3 VAC, (peak values: - 4.5…+ 4.5V)

-

You can see a voltage level for all hoist motors with the nominal current from the Appendix “3.1 Current
Transformer Table” of this manual

•

Measure the voltage across terminals 26 (I1-A) and 29 during hoisting and lowering, low and fast
speed. Voltage should be in between 0.5…3 VAC (peak values: - 4.5…+ 4.5VAC)

-

You can see a voltage level for all hoist motors with the nominal current from the Appendix “3.1 Current
Transformer Table” of this manual

•

Check parameter 4-7-13. Value should not be less than 0.20s.

•

Check parameter 4-7-14. Value should not be less than 0.30s.

Make sure that any other electrical loads (e.g. fans, inverters) haven’t been connected
behind the current transformer.