14.1.10

Fault Supply vol

F_SPh

Main supply fault, one phase missing
•

Check that the main voltage connects simultaneous to the control voltage

•

Check the connections of the terminals 19 (U1-1), 17 (U1-2) and 15 (U1-3)

In insulated or high impedance grounded networks, the zero level floats, causing errors in detecting
the actual supply voltage. Set parameter 4-10-3 to NO

14.1.11

Fault Phaseorder

F_Sor

Main supply fault, incorrect phase order (supervision is carried out only once after each power-
ON)
•

Check the connections of the terminals 19 (U1-1), 17 (U1-2) and 15 (U1-3)

•

Check the phase-order

•

Check the phase order of the wires through the current transformers

•

Check the connections of the current transformer

In insulated or high impedance grounded networks, the zero level floats, causing errors in detecting
the actual supply voltage. Set parameter 4-10-3 to NO

14.1.12

Fault CParameter F_CP

Internal parameter read or write fault
•

Incorrect check sum in reading the memory or internal hardware fault in the unit

14.1.13

Fault MParameter F_MP

Internal parameter read or write fault
•

Incorrect check sum in reading the memory or internal hardware fault in the unit