14.1.2 Fault Motor OT

F_OT

Hoist motor overtemperature

•

Check that 4-4-1 T1 operat. corresponds to the actual sensor of the hoist
motor

•

Check that 4-5-1 T2 operat. corresponds to the actual sensor of the hoist
motor

•

When NTC-type sensor is selected, check parameter 4-10-2 “OT limit”

•

Lowering can be allowed by setting 4-10-1 “OT run ?” = Down

•

Unplug the terminal X2 and measure the temperature sensor’s resistance
between terminal 21 and 22 also between terminal 23 and 24.

-

PTC-sensor or bimetal switch: the resistance should be less than 1kohm

-

NTC sensor: The resistance should be between 0.5kohm and 100 kohm. See
Appendix 4 “Motor temperature NTC-charts”

•

Measure the internal resistance of temperature input’s from terminal’s pins
by multimeter (disconnect the orange terminal X2)

-

When input is okay the input’s internal resistance is ~6.3 kohm.

14.1.3 Fault Int. relay

F_SR

A fault detected in the internal safety relay
•

Internal hardware fault in the unit, internal safety relay contact closed all the time.

•

Contact the manufacturer.

14.1.4 Fault RUN act.

F_Run

A fault detected in controlling the direction outputs (only two step control)
•

Feedback is ON already before the direction control (HOUT, LOUT) is activated.

•

Check the connections and wiring of terminals 1 to 19.

-

Especially for short circuits between HIN - HOUT and LIN - LOUT.

•

If external connections are correct and the fault occurs only in starts upwards, the internal upwards
control relay may be malfunctioning

•

If external connections are correct and the fault occurs only in starts downwards, the internal
downwards control relay may be malfunctioning

•

Make sure that the current transformer is correctly connected to the terminal 27 (I2-A)

•

Check that the current transformer operates correctly

Make sure that any other electrical loads (e.g. fans, inverters) haven’t been connected
behind the current transformer.

14.1.5 Fault Run FB – (2)

The hoist stops although the unit controls it to run
•

Check AIN-2 values by parameter 1-2-11

-

Normal values ~5V

-

If ~9.8V check current transformer connection

•

Check function of contactors

-

If the contactor is energized the problem is in the power line connections or the current transformer
connections, probably

•

Check the current transformer connection to the terminal 27 (I2-A)

•

Check the power line connections to the hoisting motor