Notice, Table d1: st band comparisons – GE Industrial Solutions EntelliGuard TU Trip Units User Manual

Page 100

Advertising
background image

EntelliGuard TU Trip Units: UL/ANSI Models

DEH-4567B

Appendix D: GTU Coordination Curve Settings Comparison

90

©2012 General Electric All Rights Reserved

APPENDIX D: GTU COORDINATION CURVE SETTINGS COMPARISON

NOTICE

These settings approximate settings on previous generation trip units. It is recommended to evaluate each breaker on a
case by case basis to determine if alternate settings provide improved coordination and protection versus the
approximate settings listed below.

ST Band Comparisons have been developed not to exceed max clearing time of other trip units to maintain or lower arc
flash hazard values.

Table D-1: ST Band Comparisons

Trip Unit

Function

Setting

GTU Curves within Band

GTU Curve Best
Approximating Max
Clearing Time

Supporting TCC

MVT / MVT PM
/ MVT+

LT Pickup -
MVT

0.5-1.1 in 0.05
increments

LT Pickup Values may be set
according to old setting

& Power+

LT Pickup -
Power+

0.5, .6, .7, .8, .9,
.95, 1, 1.1

LT Pickup Values may be set
according to old setting

(LSIG)

LT Delay

1

C4, C5

C5

MVT LT 1.pdf

LT Delay

2

C6, C7, C8

C7

MVT LT 2.pdf

See
Publications

LT Delay

3

C10, C11, C12, C13

C12

MVT LT 3.pdf

GES-9865

LT Delay

4

C15, C16, C17, C18

C18

MVT LT 4.pdf

GES-9863

ST Pickup -
MVT

1.5 - 9.0 in 0.5
increments

ST Pickup Values may be set
according to old setting

DES-001B

ST Pickup -
Power+

1.5, 2, 2.5, 3, 4, 5,
7, 9

ST Pickup Values may be set
according to old setting

DES-002B

ST Delay

1 (Min)

Bands 5, 6, 7

Band 6

MVT ST 1(Min).pdf

ST Delay

2 (Int)

Bands 8, 9

Band 9

MVT ST 2(Int).pdf

ST Delay

3 (Max)

Bands 10, 11

Band 11

MVT ST 3(Max).pdf

ST I

2

T

Out / Off

ST Slope = 0 (OFF)

ST Slope = 0 (OFF)

see above curves

ST I

2

T

In / On

ST Slope = 3 (Max)

ST Slope = 3 (Max)

MVT ST I2T.pdf

Inst

Dependent on
trip unit rating

Instantaneous Pickup Values
may be set according to old
setting

GF Pickup

Dependent on
trip unit rating

GF Pickup Values may be set
according to old setting

GF Delay

1 (Min)

Bands 3, 4

Band 4

MVT GF 1(Min).pdf

GF Delay

2 (Int)

Band 7

Band 7

MVT GF 2(Int).pdf

GF Delay

3 (Max)

Bands 8, 9

Band 9

MVT GF 3(Max).pdf

GF I

2

T

Out / Off

GF Slope = 0 (OFF)

ST Slope = 0 (OFF)

see above curves

GF I

2

T

In / On

GF Slope = I

2

T

GF Slope = I

2

T

MVT GF I2T.pdf