Notice, Table d1: st band comparisons – GE Industrial Solutions EntelliGuard TU Trip Units User Manual
Page 100
EntelliGuard TU Trip Units: UL/ANSI Models
DEH-4567B
Appendix D: GTU Coordination Curve Settings Comparison
90
©2012 General Electric All Rights Reserved
APPENDIX D: GTU COORDINATION CURVE SETTINGS COMPARISON
NOTICE
These settings approximate settings on previous generation trip units. It is recommended to evaluate each breaker on a
case by case basis to determine if alternate settings provide improved coordination and protection versus the
approximate settings listed below.
ST Band Comparisons have been developed not to exceed max clearing time of other trip units to maintain or lower arc
flash hazard values.
Table D-1: ST Band Comparisons
Trip Unit
Function
Setting
GTU Curves within Band
GTU Curve Best
Approximating Max
Clearing Time
Supporting TCC
MVT / MVT PM
/ MVT+
LT Pickup -
MVT
0.5-1.1 in 0.05
increments
LT Pickup Values may be set
according to old setting
& Power+
LT Pickup -
Power+
0.5, .6, .7, .8, .9,
.95, 1, 1.1
LT Pickup Values may be set
according to old setting
(LSIG)
LT Delay
1
C4, C5
C5
MVT LT 1.pdf
LT Delay
2
C6, C7, C8
C7
MVT LT 2.pdf
See
Publications
LT Delay
3
C10, C11, C12, C13
C12
MVT LT 3.pdf
GES-9865
LT Delay
4
C15, C16, C17, C18
C18
MVT LT 4.pdf
GES-9863
ST Pickup -
MVT
1.5 - 9.0 in 0.5
increments
ST Pickup Values may be set
according to old setting
DES-001B
ST Pickup -
Power+
1.5, 2, 2.5, 3, 4, 5,
7, 9
ST Pickup Values may be set
according to old setting
DES-002B
ST Delay
1 (Min)
Bands 5, 6, 7
Band 6
MVT ST 1(Min).pdf
ST Delay
2 (Int)
Bands 8, 9
Band 9
MVT ST 2(Int).pdf
ST Delay
3 (Max)
Bands 10, 11
Band 11
MVT ST 3(Max).pdf
ST I
2
T
Out / Off
ST Slope = 0 (OFF)
ST Slope = 0 (OFF)
see above curves
ST I
2
T
In / On
ST Slope = 3 (Max)
ST Slope = 3 (Max)
MVT ST I2T.pdf
Inst
Dependent on
trip unit rating
Instantaneous Pickup Values
may be set according to old
setting
GF Pickup
Dependent on
trip unit rating
GF Pickup Values may be set
according to old setting
GF Delay
1 (Min)
Bands 3, 4
Band 4
MVT GF 1(Min).pdf
GF Delay
2 (Int)
Band 7
Band 7
MVT GF 2(Int).pdf
GF Delay
3 (Max)
Bands 8, 9
Band 9
MVT GF 3(Max).pdf
GF I
2
T
Out / Off
GF Slope = 0 (OFF)
ST Slope = 0 (OFF)
see above curves
GF I
2
T
In / On
GF Slope = I
2
T
GF Slope = I
2
T
MVT GF I2T.pdf