Trip Unit Reinstallation

1.

Pull the trip unit locking lever to the right. While holding

the lever, carefully align the connector on the rear of the
trip unit with the connector in the breaker. Press down
on the trip unit while holding it near the battery cover.
When the trip unit is fully seated, slide the locking lever
back to the left.

2.

Reinstall the breaker top cover and tighten the four

#10-32 screws to 32 in-lb.

3.

Replace the trim plate and tighten the four #8-32

screws to 20 in-lb.

WavePro Circuit Breakers

Removal

1.

Open the circuit breaker and remove it from the cubicle

or substructure. Place it on a suitable work surface.

2.

For 800 A, 1600 A and 2000 A frame circuit breakers,

insert the racking handle (catalog number 568B731G1)
and move the racking mechanism to the TEST position,
as shown on the draw-out position indicator.

3.

Depress the OPEN button to close the racking door.

4.

Remove the wire forms and remove the trim plate from

the breaker.

5.

Remove the six ¼ hex head screws, securing the

escutcheon to the breaker (three at top and three at
bottom). Pull the manual-charging handle out part way,
and then slide off the escutcheon.

6.

Pull out the locking side on the right of the trip unit

mounting plate, and then pull the trip unit out carefully
disengaging the pins on the rear connector.

7.

Pull out the locking side on the right of the trip unit

mounting plate, and then pull the trip unit out carefully
disengaging the pins on the rear connector.

Reinstallation

1.

Pull out the locking side on the right of the trip unit

mounting plate. Push the trip unit into place, carefully,
engaging the 50 pin connector and lining up the
rejection posts on the rear of the trip unit with the holes
in the mounting plate. Push the locking slide to the left.

2.

Ensure the breaker racking mechanism is still in the

TEST position. Pull the manual charging handle out
partway, and then slide the handle through the slot in
the escutcheon and move escutcheon into place. Insert
the six mounting screws and tighten to 14-20 in-lb.

3.

Replace the trim plate around the escutcheon by re-

hooking the wire forms into the sides.

4.

Insert the racking handle and return the racking

mechanism to the DISC position, as shown by the draw-
out position indicator.

5.

Reinstall the circuit breaker into its cubical or

substructure.

AKR (225 A to 5000 A Frames) Circuit Breakers

1.

Open the circuit breaker by pressing the red TRIP button

on the front of the breaker escutcheon.

2.

Disconnect any secondary wire harnesses between the

breaker and the switchgear.

3.

On draw-out breakers, rack the breaker all the way out

to the DISCONNECT position.

4.

Follow the instructions on the label attached to the

PROGRAMMER RELEASE LEVER to remove the trip unit.
There are three types of mounting plates:

• Type 1: Push in the lever to release the trip unit
• Type 2: Pull out the lever to release the trip unit as

shown in Figure 13-1

• Type 3: Push down on the lever

Figure 13-1: Removing the Old Trip Unit

5.

If the breaker is equipped with a MicroVersaTrip® 9 trip

unit, the 36-pin trip unit connector must be removed
and remounted on the adapter bracket provided. Slide
the connector out of the mounting plate and install it on
the adapter bracket, as shown in Figure 13-2.

Figure 13-2: Circuit Breaker without Trip Unit