DEH-4567B

EntelliGuard TU Trip Units: UL/ANSI Models

Serial Communication

©2012 General Electric All Rights Reserved

51

Function Code 03H

For the EntelliGuard Trip Unit implementation of Modbus,
this function code can be used to read any setpoints
(“holding registers”). Holding registers are 16 bit (two byte)
values transmitted high order byte first. Thus all
EntelliGuard Trip Unit setpoints are sent as two bytes. The
maximum number of registers that can be read in one
transmission is 125.

The slave response to this function code is the slave
address, function code, a count of the number of data
bytes to follow, the data itself and the CRC. Each data item
is sent as a two byte number with the high order byte sent
first.

For example, consider a request for slave II to respond with
3 registers starting at address 006B. For this example the
register data in these addresses is listed below:

Table 8-1: Function Code 03H Example

Address

Data

0002

0001

0003

0000

0004

0012

The master/slave packets have the following format:

Table 8-2: Modbus Packet Format for Function Code 03H
Master
Transmission

Bytes Example

Description

Slave Address

1

11

message for slave

2

Function Code

1

03

read registers

Data Starting
Address

2

00 6B

data starting at

006B

Number of
Setpoints

2

00 03

3 registers = 6

bytes total

CRC

2

78 87

CRC error code

Slave Response

Bytes Example

Description

Slave Address

1

11

message from

slave 17

Function Code

1

03

read registers

Byte Count

1

06

3 registers = 6

bytes

Data 1 (see
definition above)

2

02 2B

value in address

006B

Data 2 (see
definition above)

2

00 00

value in address

006C

Data 3 (see
definition above)

2

00 64

value in address

006D

CRC

2

54 83

CRC error code

Function Code 04H

Modbus

Implementation:

Read Input Registers.

EntelliGuard Trip

Unit implementation:

Read Actual Values

For the EntelliGuard Trip Unit implementation of Modbus,
this function code can be used to read any actual values
(“input registers”). Input registers are 16 bit (two byte)
values transmitted high order byte first. Thus all
EntelliGuard Trip Unit Actual Values are sent as two bytes.
The maximum number of registers that can be read in one
transmission is 125.

The slave response to this function code is the slave
address, function code, a count of the data bytes to follow,
the data itself and the CRC. Each data item is sent as a two
byte number with the high order byte sent first.

For example, request slave 17 to respond with 1 register
starting at address 0008. For this example the value in this
register (0008) is 0000.

Table 8-3: Modbus Packet Format for Function Code 04H

Master
Transmission

Bytes Example

Description

Slave Address

1

11

message for slave

17

Function Code

1

04

read registers

Data Starting
Address

2

00 08

data starting at

0008

Number of Actual
Values

2

00 01

1 register = 2

bytes

CRC

2

B2 98

CRC error code

Slave Response

Bytes Example

Description

Slave Address

1

11

message from

slave 17

Function Code

1

04

read registers

Byte Count

1

02

1 register = 2

bytes

Data (see
definition above)

2

00 00

value in address

0008

CRC

2

78 F3

CRC error code

Function Code 05H

Modbus Implementation:
Force Single Coil

EntelliGuard Trip Unit Implementation:
Execute Operation

This function code allows the master to request an
EntelliGuard Trip Unit to perform specific command
operations.

For example, to request slave 17 to execute operation code
108 (Trip Breaker), we have the following master/slave
packet format: