Profibus gtu dp cyclic data, Gtu cyclic read telegram definitions, Table 91: gtu cyclic read telegram definitions – GE Industrial Solutions EntelliGuard TU Trip Units User Manual

Page 66: Cyclic read telegram id, Parameter, No. of bytes, Units, B5020, Temperature input 1, B5021

Advertising
background image

EntelliGuard TU Trip Units: UL/ANSI Models

DEH-4567B

Profibus Communication

56

©2012 General Electric All Rights Reserved

The Profibus bus address (MAC ID) of the GTU slave, which
has a range from 1 to 125, can be set via the front cover
switches. At power up, the GTU reads its address from the
two rotary switches on its front and initializes the bus
communication. Changes of the station address take effect
with the next reset or power up.

The GTU supports auto-baud rate detection. The available
baud rates and other slave specific information needed for
configuration are in the GTU GSD file, which is used by a
network configuration program.

To communicate with a Class 1 master (PLC) in a system,
the GTU GSD file is required.

PROFIBUS GTU DP CYCLIC DATA

The cyclic data is a fast process data transfer between the
Profibus DP master and the slave, which occurs once in
every DP cycle. GTU is a modular device supporting up to
144 bytes of input data.

Modules define a block size of input and output data to be
read by the master, starting from offset zero. During the
network configuration session, modules with varying sizes
of input data are provided in the GSD file.

GTU CYCLIC READ TELEGRAM DEFINITIONS
Table 9-1: GTU Cyclic Read Telegram Definitions

Cyclic Read

Telegram ID

Parameter

No. of

Bytes Units

B5020

Temperature Input 1

2

B5021

Temperature Input 2

2

B5022

Temperature Input 3

2

B5023

Temperature Input 4

2

B5024

Voltage Phase A

2

B5025

Voltage Phase B

2

B5026

Voltage Phase C

2

B5027

Current Phase A

4

B5028

Current Phase B

4

B5029

Current Phase C

4

B5030

Current Phase N

4

B5031

Energy Total

8

B5032

Energy Rollover Count

2

B5033

Power Factor Phase A

2

B5034

Power Factor Phase B

2

B5035

Power Factor Phase C

2

B5036

Power Factor Total

2

B5037

Power Real Phase A

2

B5038

Power Real Phase B

2

B5039

Power Real Phase C

2

B5040

Power Real Total

2

B5041

Power Reactive Phase A

2

B5042

Power Reactive Phase B

2

B5043

Power Reactive Phase C

2

B5044

Power Reactive Total

2

B5045

Power Apparent Phase A

2

B5046

Power Apparent Phase B

2

B5047

Power Apparent Phase C

2

B5048

Power Apparent Total

2

B5049

Power Demand Total

2

B5050

Frequency Measured

2

B5051

Longtime Pickup Status

2

B5052

Discrete Flags

6

The following tables describe the 6 bytes of GTU discrete flags cyclic input data provided in the GSD file:

Table 9-2: Byte 1

Shunt 1 Trip

Status

Bell Alarm/

Lockout

Actuation

Bell Alarm

Actuation

Input 4

Status

Input 3

Status

Input 2

Status

Input 1

Status

Relay 4

Status

15

14

13

12

11

10

9

8

B1_7

B1_6

B1_5

B1_4

B1_3

B1_2

B1_1

B1_0

1

1

1

1

1

1

1

1

255