Table c3: commands – GE Industrial Solutions EntelliGuard TU Trip Units User Manual

Page 98

Advertising
background image

EntelliGuard TU Trip Units: UL/ANSI Models

DEH-4567B

Appendix C: Modbus Register Map

88

©2012 General Electric All Rights Reserved

Table C-3: Commands

Register

Address

Modicon

Address

Parameter

Values

Implemented

Set

Get

103

104

Save Real Time Clock Registers

Yes

NA

104

105

Read Real Time Clock Registers

Yes

NA

105

106

Save EPROM Data

Yes

NA

107

108

Upload to BIM

Yes

NA

108

109

Trip Breaker

0 - Reset
1 - Trip

Yes

Yes

110

111

Profibus Status

0 - Disable
1 - Enable

Yes

Yes

111

112

Fan State / Command Close Coil
C/D: Fan state
EntelliGuard G: activate CCC Module

0 - Off
1 - On

Yes

Yes

112

113

Relay 1 state

0 - Off
1 - On

Yes

Yes

113

114

Relay 2 state

0 - Off
1 - On

Yes

Yes

114

115

Relay 3 state

0 - Off
1 - On

Yes

Yes

115

116

Relay 4 state

0 - Off
1 - On

Yes

Yes

116

117

Clear All Events

Yes

NA

117

118

Clear EEPROM

Yes

NA

118

119

Clear Energy Total

Yes

NA

119

120

Clear All Trip Counters

Yes

NA

120

121

Clear LT Trip Counter

Yes

NA

121

122

Clear All Pickup Counters

Yes

NA

122

123

Clear Short Time Trip Count

Yes

NA

123

124

Clear Instantaneous Trip Count

Yes

NA

124

125

Clear Ground Sum and CT Fault Trip Counts

Yes

NA

126

127

Clear Power Reversal Trip Count

Yes

NA

127

128

Clear Voltage Unbalance Trip Count

Yes

NA

128

129

Clear Under Voltage Trip Count

Yes

NA

129

130

Clear Current unbalance Trip Count

Yes

NA

130

131

Clear Overvoltage trip Count

Yes

NA

131

132

Clear Undervoltage Release 1 Trip Count

Yes

NA

132

133

Clear Undervoltage Release 2 Trip Count

Yes

NA

133

134

Clear Shunt 1 Trip Count

Yes

NA

134

135

Clear Shunt 2 Trip Count

Yes

NA

143

144

Trigger Waveform Capture

Yes

NA

144

145

Clear Waveform Capture Data Buffer

Yes

NA

145

146

Clear Error Counter
Same as 116. Will clear Event Log also

Yes

NA