Table 23: short time commit times, Time band, 60 hzansi, ul489 – GE Industrial Solutions EntelliGuard TU Trip Units User Manual

Page 20: 50 hzansi, ul489, 025 sec, 030 sec, 033 sec, 040 sec, 042 sec, 050 sec

Advertising
background image

EntelliGuard TU Trip Units: UL/ANSI Models

DEH-4567B

Protection

10

©2012 General Electric All Rights Reserved

Table 2-3: Short Time Commit Times

Time Band

60 Hz

ANSI, UL489

50 Hz

ANSI, UL489

1

0.025 sec

0.030 sec

2

0.033 sec

0.040 sec

3

0.042 sec

0.050 sec

4

0.058 sec

0.060 sec

5

0.092 sec

0.090 sec

6

0.117 sec

0.120 sec

7

0.158 sec

0.160 sec

8

0.183 sec

0.180 sec

9

0.217 sec

0.220 sec

10

0.350 sec

0.350 sec

11

0.417 sec

0.420 sec

12

0.517 sec

0.520 sec

13

0.617 sec

0.620 sec

14

0.717 sec

0.720 sec

15

0.817 sec

0.820 sec

16

0.917 sec

0.920 sec

17

0.933 sec

0.940 sec

Table 2-4: Short Time Settings by Breaker Type and
Frame

Breaker

Available Settings

Power Break I, Power
Break II, WavePro, AKR
conversion kits

OFF, 1.5 to 9, steps of 0.5

AKR and WavePro 5000A
frame

OFF, 1.5 to 7, steps of 0.5

EntelliGuard G Frame 1
and 2

OFF, 1.5 to 12, steps of 0.5

EntelliGuard G Frame 3

OFF, 1.5 to 10, steps of 0.5

Short Time Delay

The Short Time Delay setting consists of both a slope
setting and a fixed delay band setting. The slope and delay
are independently selectable. The slope setting consists of
three I

2

T slopes (minimum (1), intermediate (2) and

maximum (3)) and fixed delay. The fixed delay bands
consist of 11 constant time bands. The width of the bands
varies by circuit breaker and with frequency. See Table 2-4.

On all ANSI and IEC breakers, the Short Time can be
disabled by setting the Short Time Delay to “OFF”. Note that
if Instantaneous is set to “OFF” Short Time cannot be
turned off.

Figure 2-4: Short Time Delay

Short Time Slope

The slope setting modifies the initial portion of the ST delay
band in the familiar “hockey stick” configuration. A setting
of OFF puts the constant time band in effect, with no slope.
Slope settings of 1, 2, or 3 put progressively higher slope
values in effect. If the fault exceeds the sloped section of
the curve, the constant time band setting takes effect.

Table 2-5: Short Time Delay Settings

Band Time Delay

Band Setting

Commit Time

EntelliGuard G

50 Hz

60 Hz

Clear

Time

60 Hz

Clear

Time

50 Hz

1

Min.

0.030

0.025

0.080

0.085

2

2nd

0.040

0.033

0.088

0.093

3

3rd

0.050

0.042

0.097

0.102

4

4th

0.060

0.058

0.113

0.118

5

5th

0.110

0.092

0.147

0.152

6

6th

0.130

0.117

0.172

0.177

7

7th

0.180

0.158

0.213

0.218

8

8th

0.210

0.183

0.238

0.243

9

9th

0.240

0.217

0.272

0.277

10

10th

0.280

0.350

0.405

0.410

11

Max.

0.340

0.417

0.472

0.477

• Short Time slope is forced to OFF when optional LT Fuse (i

4

t) curves are

in use.

Slope OFF

Slope = 3

Slope = 1