GE Industrial Solutions CPS6000 User Manual

Page 198

Advertising
background image

CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

198

Alarm Relays

LED

LED

Alarm / Event

Description

Default

Setting

Range /

Severity

PMJ PMN Relay

1

Relay

2

Relay

3

Relay

4

PMJ PMNNORM AUXMD

Red Yellow Green

Red

Auxiliary Major
Alarm

Alarm asserted when the controller
detects a contact closure between pins
23 and 24 of the host-interface. The
alarm is used to represent a failure in
external equipment.

Major Major/

Minor/RO

x

x

Battery on
Discharge

Voltage threshold generally used to
indicate the system is completely or
partially operating on battery power has
been reached. System batteries are
discharging.

51.1V
Major

46-55V
Major/
Minor/RO

x

o

x

Check Battery Alarm asserted when battery does not

pass the manual, automatic or periodic
discharge tests. Manual discharge tests
must be user invoked.

Minor Major/

Minor/RO

x

x

Circuit Pack
Failure

External Modem can not be initialized. Minor

Major/
Minor/RO

x

x

Clock Battery
Low

The controller internal RAM backup
battery is low and requires replacement.

RO Major/

Minor/RO

x

x

Comm Loss
Major

Alarm asserted when controller loses
communication with multiple serially
rectifiers or the LVD board. This alarm
is masked for the rectifier if the ACF or
RFA alarms are detected prior to loss of
communications in the failed rectifier.

Major Major/

Minor/RO

x

x

Comm Loss
Minor

Alarm asserted when the controller can
not detect a single serially connected
rectifier or any number of thermal
probes that was previously connected.

Minor Major/

Minor/RO

x

x

Controller
Ambient
Temperature
High

Controller on-board ambient
temperature measurement has reached
the configured high ambient
temperature threshold.

75°C
Minor

35-75 °C
Major/
Minor/RO

x

x

Controller
Ambient
Temperature
Low

Controller on-board ambient
temperature measurement has reached
the configured low ambient temperature
threshold.

-40°C
Minor

-40-10 °C
Major/
Minor/RO

x

x

Controller Fail Controller has power and has failed.

Implemented in hardware.

N/A

N/A

x

x

x

x

Defective Temp
Probe

Controller determines a “1-wire” probe
to be defective.

Minor Major/

Minor/RO

x

x

Fan Fail

One or more rectifiers has reported a
failed fan

Major Major/

Minor/RO

x

x

Fuse Major

An input that has been properly
configured and mapped as a Fuse Alarm
Major has been detected.

Major Major/

Minor/RO

x

x

Fuse Minor

An input that has been properly
configured and mapped as a Fuse Alarm
Minor has been detected.

Minor Major/

Minor/RO

x

x

Advertising