GE Industrial Solutions CPS6000 User Manual

Page 74

Advertising
background image

CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

74

Terminate Load Connections - Direct to Bus
Connections

The Distribution Module can be connected directly to the unprotected (no fuses or circuit
breakers) dc output bus. Connections are made from the top of the unit. Lug covers are not
provided they must be ordered separately.

Warning: Cables terminated directly to the DC output bus in Figure 5-25 are unfused. Ensure
cables ends are protected before terminating cables.

Step Action

1.

Terminate 45° lugs (with 1/4-inch holes on 5/8-inch centers) to bus landings
(hot spots) and torque M6 screws to 65 in-lbs. (7.3Nm).

2.

Break tabs off back of lug cover (see Figure 5-25).

3.

Insert the front post of the lug cover into the mounting hold and snap the tab
on the back of the lug cover into place.

Figure 5-25: Direct Connection to V+ (shown) / V- Output Bus