GE Industrial Solutions CPS6000 User Manual

Page 22

Advertising
background image

CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

22

Table 2-J: QS820A Ringer Specifications

Input Voltage

-40 to -57 Vdc See Output VA Thermal Limiting.

Nominal Input Voltage

-48 Vdc

Input Current

5 A max.

Output
Voltage

ac Component

65 to 100 Vac
Factory Default: 100Vac

ac tolerance

± 5 Vac

Regulation

±5% ac component only

dc

Offset


Type of ringing
Battery Backed
Ground Backed
Ground Backed no-dc

• -40 to +57 Vdc Battery Backed

• +40 to +57 Vdc

Ground Backed

• 0 Vdc Offset Disabled

• dc Offset tracks dc Input Voltage

• Factory Default: Enabled

• Battery or Ground Backed is selected by Ringer

Chassis jumper J12 or by external connection of
Ring Rtn to Battery or to Ground. Factory Default:
Battery Backed by Jumper

See figures in the Ringer section.

dc

Offset

Tracking

Error

± 3 Vdc

Harmonic

Distortion

5%

THD

Crest Factor

1.21 to 1.51

Output Frequency

15 to 50 Hz
Factory Default: 20 Hz

Frequency tolerance

± 1 Hz

Output VA

100 VA

Thermal Limiting

Output VA may be reduced by reducing Vac when
operating simultaneously above 50°C and less than
-50Vdc input.
Vac is reduced only sufficiently to prevent damage to
the ringer.

Load Power Factor

Operating: 0.5 Leading to 0.9 Lagging
No Damage: 0 Leading to 0.7 Lagging

Operating Temperature

-40 to +75 °C See Output VA Thermal Limiting.

Heat Dissipation

50 W (170 BTU / hr)

Under Voltage Shutdown

50% of Output Vac Set Point
While shutdown due to external fault, restart will be
performed at approximately 2 minute intervals.

Table 2-K: QS840A and QS841A Control Unit Specifications

Operating Input Voltage Range

38 to 60 Vdc

Input Power

6.0 watts maximum

Plant Parameter Setting

Through front panel LCD display and menu keys or with
IBM compatible PC with RS-232 port. 841 also has 10/100
Baset-T network ability

Alarm Contact Ratings

60 Vdc, 0.5A, Form-C

Operating Temperature

-40 to +75 °C