CPS6000 –48V Indoor/Outdoor Power Shelf


Issue 21 January 2008

83

Serial Port
The appropriate IP address, subnet mask, hostname, and default gateway IP
address must be configured on the QS841A through serial port J3.

To login to the QS841A, follow these steps:

a. Start-up the PC terminal program (Windows Terminal,

ProComm, etc.) using the following communication
parameters:

Baud : 9600
Data : 8
Parity : none
Stop : 1
Handshaking: none
Flow Control: none

b. Connect the PC to the QS841A local port (RS-232) connector

J3

c. Wait for any diagnostic messages to pass.
d. Wait for the “ENTER PASSWORD:” command line prompt.
e. Type the Network Administrator password (default:

administrator).

f.

Wait for the “$” prompt.

8A Configuring

Static Network Parameters

After a valid password entry, a login header with the following format similar
to that below will be displayed:

Board Code

QS841A

Serial Number 05DJ09112345

Boot Block

version 1.0

Application Code

version 1.0

Default Web Pages

version 1.0

Custom Web Pages

not found


Ethernet Address

00-60-1D-00-5C-07

IP Address

not configured

Subnet Mask not configured
Default Gateway

not configured

Host Name

not configured


For assistance type help

$

Typing HELP at the “$” will show all available network administration
commands and command line formats.

*note: 1) commands are not case sensitive
2) for the commands that follow, ddd is a number from 0 – 255

• To set the IP Address, type: