ASTAT BP User Manual

103

GE Industrial Solutions

©2013 GE Company All Rights Reserved

C.1.5.

Rotary Switch Configuration

Two rotary switches configure the DeviceNet MacID, and one rotary switch configures the baud rate. Use a

small screwdriver to change the switch settings. The NODE ADDRESS (MAC ID) rotary switches are shown in

Figure 1, and the DATA RATE rotary switch is shown Figure 2.

Figure 1

MAC ID rotary switch layout

Use the NODE ADDRESS switches to select the DeviceNet MAC ID address. The valid range of addresses is 0 –

63. All combinations above 63 set the device address to the last address the device was powered up at and

allow software configuration tools to modify the MAC ID address.

Figure 2

Baud rate rotary switch layout

Rotary switch S1 (BAUD) is used to select the DeviceNet Baud Rate. The valid range of baud rates is 1 (125K), 2

(250K), 5 (500K), and P (programmable). All values P and above set the baud rate to the last baud rate the

device was powered up at and allow software configuration tools to modify the baud rate.

Factory default settings for the rotary switches are typically Address 63, 125K.

C.1.6.

LED Indicators

The DeviceNet Gateway provides support for three LEDs: Serial Status (Modbus Diagnostic), Network Status,

and Module Status. The LED on the right indicates the current Serial or Modbus Diagnostic status. The

operation of the Modbus LED is described in Table 1.

Table 1

Modbus Diagnostic Status LED

Color

State

Indication

None

Off

No power

Red

Flashing

Modbus Timeout

Orange

Flashing

Modbus Error

Green

Flashing

Normal operation


0

MSD LSD

4

2

6

4

0

2

6

8

ADDRESS

P

125Kb

250Kb

500Kb

PGM

DATA RATE