GE Industrial Solutions ASTAT BP User Manual

Page 60

Advertising
background image

ASTAT BP User Manual

60

GE Industrial Solutions

©2013 GE Company All Rights Reserved

Notes:

(1) - Use fuses/circuit breaker for type 1 coordination. Refer to section

Error! Reference source

not found. on page Error! Bookmark not defined.

(2) - Use fuses for type 2 coordination. Refer to section

Error! Reference source not found. on

page

Error! Bookmark not defined.

(3) - For Aux. input programming refer to section 4.7.8 on page 39

Note: The use of solid state relays to control the digital inputs B1 and C1 is prohibited

(4) – Close auxiliary contact between F1 to F2 when fan control is required. Only possible when

fans are installed (only available in QBx210-QBx1100).

Do not remove this jumper unless

consulting factory!!!

(5) - For Aux. output programming refer to section 4.7.8 on page 39
(6) - Fault relay can function as a “Fault” relay or as a “Fail-Safe” relay. For Fault relay

programming refer to section 4.7.8 on page 39

(7) - When emergency Stop switch is required it is recommended to trip a series contactor or the

feeding circuit breaker. (Not shown)

(8) – Mains voltage of 208-600V available to all models. (need to be specified)

(9) - 1L1, 3L2, 5L3, 2T1, 3T2 and 6T3 Bus bars are made of aluminium. Suitable connection

method should be applied.

88..22

Operating With Momentary Start and Maintained Stop Contacts

Aux. input terminal C1 is a

maintained/momentary

stop input to the ASTAT-BP, while Input terminal B1 is a

momentary start input to the ASTAT-BP.

In order to operate this way:

o Program PROG. Input C1 to START/STOP. Refer to section 4.7.8 page 39.

o Wire the ASTAT-BP as shown in the drawing above. Switch A (momentary NO) is used as a local start,

switch B (

momentary/maintained

NC) can be used as local soft stop command that also prevents an

unwanted remote start coming from communication.

88..33

Operating via Communication Links

•

In order to operate via communication, either Modbus (standard) or Profibus (optional) or DeviceNet

(optional) optional PCBs must be installed and wired properly.

•

ASTAT-BP must be properly grounded.

•

ASTAT-BP must be programmed to enable control (not only monitoring). Refer to section 4.7.9, 4.7.11

and 4.7.12 page 42 for programming.

•

Make sure that after programming, Control Supply voltage (terminals A1 and A2) is disconnected and

reconnected so that the communication settings will take affect.

•

ASTAT-BP can now be operated via communication.

•

If required to have a wired interlock to avoid communication start do the following:

o Program PROG. Input C1 to START/STOP. Refer to section 4.7.8 page 39.

o Wire the ASTAT-BP as shown in the drawing below. Switch A can be used as a local start, switch

B can be used as local soft stop command that also prevents an unwanted remote start coming

from communication.

Advertising