Terminal

Function

Description

When the

At Fault Close function is selected, the relay is

energized upon fault. The contact returns to its original position

when one of the following occurs:

• The fault has been removed and ASTAT-BP was reset.

• Disconnection of Control Supply

When the

At Fault Open function is selected, the relay is

energized immediately when the Control Supply is connected and

de-energizes when one of the following occurs:

• Fault

• Control Supply disconnection

Refer to section 4.7.8 page 39 for

PROG. Fault Relay

programming.

Terminal D-

RS-485 communication (-)

• Standard RS485, half duplex with Modbus protocol, baud rate

1200, 2400, 4800, 9600 BPS.

Terminal D+

RS-485 communication (+)

• Twisted shielded pair should be used.

Connect shield to ground on the PLC/Computer side.

Terminal 28

Thermistor input (T1)

• Up to 32 units can be connected for Modbus RS485

communication. For reliable communication, units should be

installed in the vicinity of 200m maximum, from the first to the last

unit.

• Refer to section 4.7.9 page 41 for programming.

• Refer to section 8.1 page 59 for wiring diagram and more details.

• Refer to Appendix A of this manual for Modbus protocol manual.

Terminal 29

Thermistor input (T2)

Thermistor input is programmable as a PTC or NTC type thermistor.

The trip value is adjustable between 1-10Kohm, preset delay of 2

Sec.

Terminal 30

Ground

Connect thermistor and/or Analog output shield to ground terminal.

Terminal 31

Analog output (-)

Analog output (0-10VDC or 0-20mA or 4-20mA)

Terminal 32

Analog output (+)

Reflects motor current and is related to 2xIm. i.e., Full scale (10VDC

or 20mA) is related to 2xIm.

D-9 connector

Profibus communication (optional)

Note:

Refer to section 5.6 page 49 for analog output PCB dip switch

setting.

• Refer to section 4.7.8 page 39 for

Analog Output

programming.

• Refer to section 4.7.7 page 37 for

Thermistor Type and

Thermistor Trip programming.

D-9 connector

Remote keypad

Connect the D-9 connector supplied with the optional emote

keypad to this connector

Terminal V-

DeviceNet communication

(optional)

• Profibus DPV0 and DPV1, up to 12 MBPS.

• D type 9 pin connector is applied.

• Control, monitoring and setting parameters can be achieved via

the Profibus connection.

• Setting is possible only when DPV1 is implemented.

• Refer to section 4.7.11 page 42 for programming.

• Refer to Appendix B of this manual for Profibus protocol manual.

Terminal CL

DeviceNet communication

(optional)

0 Volt external power supply

Terminal Dr

Negative data line

Terminal CH

Cable shield

Terminal V+

Positive data line

+24V external power supply