Terminal function description – GE Industrial Solutions ASTAT BP User Manual
Page 15
ASTAT BP User Manual
15
GE Industrial Solutions
©2013 GE Company All Rights Reserved
Terminal
Function
Description
When the
At Fault Close function is selected, the relay is
energized upon fault. The contact returns to its original position
when one of the following occurs:
• The fault has been removed and ASTAT-BP was reset.
• Disconnection of Control Supply
When the
At Fault Open function is selected, the relay is
energized immediately when the Control Supply is connected and
de-energizes when one of the following occurs:
• Fault
• Control Supply disconnection
Refer to section 4.7.8 page 39 for
PROG. Fault Relay
programming.
Terminal D-
RS-485 communication (-)
• Standard RS485, half duplex with Modbus protocol, baud rate
1200, 2400, 4800, 9600 BPS.
Terminal D+
RS-485 communication (+)
• Twisted shielded pair should be used.
Connect shield to ground on the PLC/Computer side.
Terminal 28
Thermistor input (T1)
• Up to 32 units can be connected for Modbus RS485
communication. For reliable communication, units should be
installed in the vicinity of 200m maximum, from the first to the last
unit.
• Refer to section 4.7.9 page 41 for programming.
• Refer to section 8.1 page 59 for wiring diagram and more details.
• Refer to Appendix A of this manual for Modbus protocol manual.
Terminal 29
Thermistor input (T2)
Thermistor input is programmable as a PTC or NTC type thermistor.
The trip value is adjustable between 1-10Kohm, preset delay of 2
Sec.
Terminal 30
Ground
Connect thermistor and/or Analog output shield to ground terminal.
Terminal 31
Analog output (-)
Analog output (0-10VDC or 0-20mA or 4-20mA)
Terminal 32
Analog output (+)
Reflects motor current and is related to 2xIm. i.e., Full scale (10VDC
or 20mA) is related to 2xIm.
D-9 connector
Profibus communication (optional)
Note:
Refer to section 5.6 page 49 for analog output PCB dip switch
setting.
• Refer to section 4.7.8 page 39 for
Analog Output
programming.
• Refer to section 4.7.7 page 37 for
Thermistor Type and
Thermistor Trip programming.
D-9 connector
Remote keypad
Connect the D-9 connector supplied with the optional emote
keypad to this connector
Terminal V-
DeviceNet communication
(optional)
• Profibus DPV0 and DPV1, up to 12 MBPS.
• D type 9 pin connector is applied.
• Control, monitoring and setting parameters can be achieved via
the Profibus connection.
• Setting is possible only when DPV1 is implemented.
• Refer to section 4.7.11 page 42 for programming.
• Refer to Appendix B of this manual for Profibus protocol manual.
Terminal CL
DeviceNet communication
(optional)
0 Volt external power supply
Terminal Dr
Negative data line
Terminal CH
Cable shield
Terminal V+
Positive data line
+24V external power supply