8.7.5

ASTAT-BP Connected Inside Delta - Reverse Speed

IMPORTANT! If speed reversing is required, L1, L2 and L3 on the input of the ASTAT-BP can not be switched!

This is because

Phase Sequence Disabled can not be implemented when ASTAT-BP is connected Inside

Delta. Thus, in order to reverse motor rotation two motor windings need to be switched as shown in the

following diagram:

(Winding V1-V2 is switched with winding U1-U2):

Reverse speed with ASTAT-BP connection Inside Delta with bypass contactor
to the ASTAT-BP and Inside Delta contactor.

C1 is an Inside Delta contactor.

U1-U2, V1-V2, W1-W2 are motor windings.

1L1-2T1, 3L2-4T2, 5L3-6T3 are ASTAT-BP controlled phases.