GE Industrial Solutions ASTAT BP User Manual

Page 39

Advertising
background image

ASTAT BP User Manual

39

GE Industrial Solutions

©2013 GE Company All Rights Reserved

4.7.8

I/O Settings Parameters

34

– Page 7

Function &

Default

Range

Unit

Description

PROG. Input C1

Reset

START/STOP;

Reset;

External Fault;

Slow

Spd/Reverse;

GEN.START/STOP;

Dual Settings

Sets terminal C1 function

Refer to section 4.7.8.1 on page 41.

PROG. Fault Relay

At Fault Close

At Fault Close,

At Fault Open

Sets the Fault Relay mode of operation.

When configured to

At Fault Close the internal

relay is energized upon fault.

When configured to

At Fault Open the relay is

de-energized upon fault. In this mode, while normal

operation, the fault relay is energized.

Relay will also de-energize upon control power

outage.

PROG. AUX. RELAY

IMMEDIATE

IMMEDIATE/Eor

Relay

When set as: Immediate Relay (RUN relay):

The relay is energized upon the START signal.

The relay is de-energized when one of the following

occurs: Fault, Control Supply outage or STOP signal.

When SOFT STOP is operated - the relay is de-

energized at the end of the SOFT STOP process.

The Immediate Relay (RUN relay) can be used for the

following purposes: Release a brake of a motor,

Interlock with other systems, Signalling, Delay the

opening of a line contactor at the end of SOFT STOP,

thus allowing current to decrease to zero before

opening the contactor or to switch to / from DUAL

settings with a time delay from the START signal (see

Special Starting section 6.2.3.1 page 54).

The relay incorporates ON and OFF delays of 0-60

sec. each.

When set as: EOR Relay (End Of Ramp relay):

Changes its position at the end of ramp, after an

adjustable time delay (Contact Delay), 0 – 60 sec.

The contact returns to its original position when Soft

Stop or Stop signals, on Fault condition, or upon

voltage outage.

The EOR (End Of Ramp) contact can be used for:

-Activating a valve after compressor has reached full

speed

-Loading a conveyor after motor reached full speed.

Relay ON Delay

0 SEC.

0 – 60

sec.

Sets ASTAT-BP’s auxiliary relay ON Delay.

34

Displays in MAXIMIZED MODE only. To change to this mode refer to parameter DISPLAY MODE on section 4.7.2 page 26.