VFD to go into “Bypass Mode” which means they
will operate as fixed-speed pumps.

Start: Start a specified combo when the difference
between the actual pressure and user defined SP
exceeds this value.

Stop: Stop a specified combo when the difference
between the actual pressure and user defined SP
exceeds this value.

Tap [Next] to move to the next Field Setup screen.

Figure 50: Combos

Combo Pumps
This screen allows you to configure which pump will
be used in which combo.

Tap [Next] to move to the next Field Setup screen.

Figure 51: Combo Pumps

AUXILIARY SETUP

Tap [Auxiliary Setup] from the Setup menu.

These screens allow you to setup and configure
any auxiliary equipment. Check any auxiliary
equipment that needs to be set up.

Each enabled item requires an IP address to
communicate to the PLC using the Modbus
protocol, which can be entered by double clicking
on the IP address field.

Default IP addresses can be found in Appendix E.

Note: Pace 5.0+ supports integrated auximilary
equipment. Setting the IP address of the auxiliary
equipment to the same as the main PLC enables
the integrated auxiliary device.