3. FLANGE ALIGNMENT AND LOADING

Angular alignment of the suction and discharge

flanges can best be accomplished using calipers at the

bolt locations. See figure below.

NOTICE: DO NOT DRAW PIPING INTO PLACE BY

FORCING THE PUMP SUCTION OR DIS-

CHARGE CONNECTIONS.

4. PIPING

Discharge and suction piping should be no smaller

than the respective pump opening and should be

kept as short as possible, avoiding unnecessary

fittings to minimize friction losses.

NOTICE: PIPING MUST BE INDEPENDENTLY SUP-

PORTED AND NOT PLACE ANY PIPING

LOADS ON THE PUMP.

If suction piping larger than pump suction is re-

quired, an eccentric pipe reducer, WITH THE

STRAIGHT SIDE UP, must be installed at the pump

suction.
If the pump is installed below the liquid source,

install a full flow isolation valve in the suction piping

for pump inspection or maintenance.

NOTICE: DO NOT USE THE ISOLATION VALVE

ON THE SUCTION SIDE OF THE PUMP

TO THROTTLE PUMP. THIS MAY CAUSE

LOSS OF PRIME, EXCESSIVE TEMPERA-

TURES, DAMAGE TO PUMP AND VOID

WARRANTY.

If pump is installed above the liquid source, the

following MUST be provided:

To avoid air pockets, no part of the suction pip-

ing should be above the pump suction.
On any horizontal piping sections, slope piping

upward from liquid source.
All suction pipe joints MUST be airtight.
Use a foot valve for priming, or for holding

prime during intermittent duty.

The suction strainer or suction bell MUST be at least

3 times the suction pipe diameter.
Insure that the size and minimum liquid submer-

gence, over the suction inlet, is sufficient to prevent

air from entering through a suction vortex. See typi-

cal suction piping Figures 1 through 4.
Install a discharge check valve, suitable to handle the

flow and liquids, to prevent backflow.
Install an appropriately sized gate valve, AFTER the

discharge valve, to regulate the pump capacity, for

pump inspection and for maintenance.
When a pipe increaser is required, install between

the check valve and the pump discharge.

5. SHAFT ALIGNMENT – MOTOR TO PUMP

When the pump is purchased less motor, the pump

will be supplied with a motor assembly shim posi-

tioned between the motor adapter and the coupling.
To assemble the motor to the pump remove the

plastic shipping straps, the 2 stainless steel coupling

guard halves, and the expanded polyurethane.
Insure that the motor assembly shim is properly posi-

tioned between the coupling and the motor adapter.

If the motor assembly shim is not available, a 0.203"

(5 mm) shim may be used to locate the pump shaft

assembly and to set the correct height. See figures

below.

Figure 1

Figure 2

Figure 3

Figure 4

H min.

D

H min.

16
15
14
13
12
11
10

9
8
7
6
5
4
3
2
1
0

H = Min.

Submer

gence in feet

8D

min.

4D

min.

= GPM x 0.321

Area

GPM x 0.4085

D

2

min.

3D

2

V = Velocity in feet per second

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 V

H

H min.