SECTION 6: POWER SUPPLY AND WIRING

(CONTINUED)

CONTROL TERMINAL CONNECTION DIAGRAM

The diagram below describes the control terminal connections.

NOTE

A jumper wire is installed between DI1 and +24V at the factory. To remotely start and stop the drive while in
REM mode, replace the jumper wire with a non-powered switch.

Identification

RELAY OUTPUTS R04 TO R06

1 RO4C
2 RO4A

Relay output

3 RO4B

Default operation: Started

4 RO5C
5 RO5A

Relay output

6 RO5B

Default operation: Running

7 RO6C
8

RO6A

Relay output

9 RO6B

Default operation: Fault

FIGURE 4

NOTE

Pressure sensor cable must be wired during installation. All other connections are wired at the factory.