Xylem IM244R04 SPD Plus Variable Speed Pump Control User Manual

Page 16

Advertising
background image

16

SECTION 6: POWER SUPPLY AND WIRING

(CONTINUED)

CONDUIT, WIRE AND FUSE SIZING
When selecting the input power cable follow the rules
below:

• Do not use aluminum wires
• The cable must be able to carry the drive load

current

• The cable must be rated for at least 75ºC
• A four conductor cable (three phases and ground)

or four insulated conductors routed through
conduit may be used. Shielding is not required.
The use of metal conduit with metal conduit
connectors is recommended for all electrical
connections. Use the NEC or CEC to determine
the required conduit size for the application.

Refer to the wire sizing tables in Appendix B to
determine the maximum length for the input and
output cables. The maximum recommended total
voltage drop on both input and output cable
combined is 5%. Standard wire sizing table provides
maximum cable lengths for input or output cables.

Because of this the lengths given in the table must be
adjusted so the total voltage drop does not exceed
5%. For example, if the input wire sizing chart in the
appendix gives the maximum length of 400' and
only 100' is used then only 25% of the total voltage
drop (1.25% drop) is used. The maximum output
cable length must then be adjusted to 75% of its
value so that the maximum voltage drop of 5% is not
exceeded.

Provide a dedicated fused disconnect rated for drives
input current rating. (Fused disconnect included for
NEMA3R enclosures.) No other equipment should be
used for this disconnect. Use fast acting class T fuses.
The recommended fuse sizes for each model are
listed below.

INPUT POWER CONNECTIONS
Before making this connection, measure and verify
the site voltage phase to phase and phase to ground.
In the case of high line to ground voltage it may be
necessary to disconnect the line to ground EMC and
MOV protection. See Figures 1, 2 and 3 for details.
Ensure the ground wire is connected back to the
service entrance ground and that the service entrance
ground is bonded to a proper ground rod.

Ensure disconnect switches
are locked in the OFF
position before making this

connection. For models with an N1 (NEMA
1) suffix, connect conduit to the conduit
box supplied with the controller. For all
other models (NEMA 3R), drill a hole that
is properly sized for the conduit used in
the bottom of the enclosure.
NOTE: Drilling in to the side or top of the
enclosure will violate the NEMA 3R rating.
Use metal conduit and metal conduit
connectors. Size the conduits according to
the NEC, CEC or local codes. Use the wire
sizing chart in Appendix B to determine
the size of the input power wires.

Connect the conduit and insert the wires
into the controller or enclosure. Connect
wires to the “INPUT” terminal block. For
N1 models, this terminal block is on the
controller and the terminal locations are
as shown in Figures 1, 2 and 3. For all
other models, this connection is made
to the input side of the fused disconnect
that is included in the enclosure. The
connections from the output side of the
disconnect to the controller are made at
the factory. Connect the ground wire to
the terminal labeled GND. For three phase
input, connect the input phase wires to
U1, V1 and W1. For single phase input,
connect the input wires to U1 and W1.

Input

Voltage

Model Number

Input Current

(Arms)

Mains Fuse Size

(UL Class T)

230V

SPD20400

114

150

SPD20400F

143

200

SPD20400N1

114

150

SPD20500

143

200

SPD20500F

178

250

SPD20500N1

143

200

SPD20600

178

250

SPD20600F

221

300

SPD20600N1

178

250

460V

SPD40400

59

80

SPD40400F

72

90

SPD40400N1

59

80

SPD40500

72

90

SPD40500F

96

125

SPD40500N1

72

90

SPD40600

96

125

SPD40600F

96

125

SPD40600N1

96

125

SPD40750

124

175

SPD40750F

124

175

SPD40750N1

124

175

SPD41000

157

200

SPD41000F

157

200

SPD41000N1

157

200

575V

SPD50400N1

52

60

SPD50500N1

77

100

SPD50600N1

77

100

SPD50750N1

99

150

SPD51000N1

144

200

Hazardous

voltage

DANGER