APPENDIX B: FUSE AND WIRE SIZING

FUSES
Branch circuit protection must be provided by the end
user and sized per national and local electric codes.
The following tables provide fuse recommendations
for short circuit protection on the drive's input power.

The rated fuse currents given in the tables are the

maximums for the mentioned fuse types. If smaller
fuse ratings are used, check that the fuse Arms current
rating is larger than the input current.

Check that the operating time of the fuse is below

0.5 seconds. The operating time depends on the
fuse type, the supply network impedance as well as
the cross-sectional area, material and length of the
supply cable. In case the 0.5 seconds operating time
is exceeded with the gG or T fuses, ultra rapid (aR)
fuses will in most cases reduce the operating time to
an acceptable level.

Input

Voltage

Model

Number

Input

Current

(Arms)

Mains

Fuse Size

(UL Class T)

230V

SPD20400

114

150

SPD20400F

143

200

SPD20400N1

114

150

SPD20500

143

200

SPD20500F

178

250

SPD20500N1

143

200

SPD20600

178

250

SPD20600F

221

300

SPD20600N1

178

250

460V

SPD40400

59

80

SPD40400F

72

90

SPD40400N1

59

80

SPD40500

72

90

SPD40500F

96

125

SPD40500N1

72

90

SPD40600

96

125

SPD40600F

96

125

SPD40600N1

96

125

SPD40750

124

175

SPD40750F

124

175

SPD40750N1

124

175

SPD41000

157

200

SPD41000F

157

200

SPD41000N1

157

200

575V

SPD50400N1

52

60

SPD50500N1

77

100

SPD50600N1

77

100

SPD50750N1

99

150

SPD51000N1

144

200