SECTION 8: STARTING THE SYSTEM

APPLY POWER

When power is applied to the SPD Plus Controller, the status LED turns green.

SPD Plus Drive keypad functionality and Main Screen display is described below:

DIR

MENU

REM

40.2 PSI sp

0.0 PSI ac

0.0 HZ

11.1%

LOC

REM

Status LED

Motor State

Reference Value

Pressure Setpoint

Actual System Pressure

Soft Key 2

Up/Down Buttons

Help Function

Start

Stop

LOC/REM

Soft Key 1

Motor Speed

Control Mode

Name

Function

Status LED

Displays Drive Status:
Green Constant = Not Faulted/No Alarm
Green Flashing = Alarm
Red Constant = Faulted (Auto-restart fault)
Red Flashing = Faulted (Locked Out)

Motor State

Rotating = Drive is Running the Motor
Stationary = Drive has Stopped the Motor

Control Mode

Displays the current control mode of the drive. In local mode (LOC) the drive ignores the pressure
sensor feedback and speed is set with the up and down buttons. In remote mode (REM) the drive
uses the pressure sensor feedback signal to control the system pressure.

Reference Value

In REM: Displays the pressure setting in %.
In LOC: Displays the speed reference in Hz.

Pressure Setpoint

Displays the system pressure setpoint in PSI.

Actual System

Pressure

Displays the actual system pressure in PSI as indicated by the pressure transducer.

Motor Speed

Actual motor speed in Hz.

Soft Key 1

Function of this button changes according to the state of the display panel.

Soft Key 2

Function of this button changes according to the state of the display panel.

LOC/REM

Toggles the drive control mode between local (LOC) and remote (REM). See Control Mode above.

Up/Down Buttons

In REM: Changes the pressure setting.
In LOC: Changes the speed reference.
In sub menus: changes parameters

Help Button

Displays information about the parameter or screen shown on the display.

Start

In REM: Button is disabled
In LOC: Initiates operation of the drive.

Stop

In REM: Button is disabled
In LOC: Stops operation of the drive.

Advertising