SECTION 8: STARTING THE SYSTEM

(CONTINUED)

START-UP ASSISTANT

If this is the first time
that the drive has been
powered or the Start-
Up Assistant has not
been run, the display
will prompt the user if
they would like to run
the Start-Up Assistant.
Select Yes using the up
and down arrows then
press OK to run the
Start-Up Assistant.

NOTE
The Start-Up Assistant can be entered at any time by
following the procedure below:

QUICKSTART: From
the Main Screen press
MENU key to enter
MENU as shown
below and choose
QUICKSTART.

START-UP: Select Start-
Up with the up and
down arrows and press
SEL.

EXIT

Do you want to

use the start-up

assistant?

YES

NO

The Start-Up Assistant will prompt the user for
information about the application, motor information
and fault response. The prompt screens are shown
below:

MOTOR TYPE

SETTING: Select the
motor type used in the
application using the
up and down arrows
and press OK.

The minimum
frequency is set
to 30Hz for the
Submersible setting
and 15Hz for the
Above Ground setting.

The next prompt will
be for either to enter
the motor horsepower

rating or the motor nominal current rating. The
prompt displayed will depend on the controller size.

MOTOR

HORSEPOWER

SETTING: Select the
motor HP used in
the application. The
controller lists only
the valid HP selections
based on the
controller size. If there
is only 1 valid selection
based on the drive
size and motor type,
this screen is skipped.
Note that the prompt
will also change based
on the controller
voltage rating.

MOTOR NOMINAL

CURRENT SETTING:
The display will initially
show a default current
based on the previous
selections. Enter the
nominal motor current
rating using the up
and down arrows on
the keypad. This is the
full load current rating
for the motor.