3 x short + 1 x long

• Voltage too low / too

high

• Check mains voltage

4 x short

• Temperature too high

• Pump restarts
automatically
(see the notes below)
• Determine max. system

temperature

2 x short + 1 x long +1 x
short

• Self test error

• Please contact

authorized service
center or point of

purchase

2 x short + 2 x long

• Excess current error

• See section 8

Maintenance/

Disassembly”

1 x short + 1 x long + 1 x

short + 1 x long

• Unstable operation

• See section 8

Maintenance/

Disassembly”

1 x short + 1 x long + 2 x
short

• Start up error

• Rotor blocked
• See section 8

Maintenance/

Disassembly”

1 x very short + 1 x long

pause

• Air purge function

• Pump runs in air purge

function / color means
mode selected


Proceed as follows for other faults:

Fault

Cause

Solution

Pump is making
loud noises

• Not thoroughly vented

• See section 7.2

“Getting

started”

• Foreign objects in

pump

• See section 8

“Maintenance/

Disassembly”

• Worn out bearing

• Replace pump

Note regarding excessive temperatures:
In order to protect the electronics from temperatures that are dangerously
high, the electronic control system monitors its own temperature. If the
measured temperature is too high the pump speed is reduced. If the