PROFIBUS error diagnosis

A simple diagnosis of the PROFIBUS communication is possible via
the measured value and status display (status online/offline, see
section 4.2).

7.7

PROFIBUS error elimination

Note
Here you will find causes and actions to take of errors concerning the
PROFIBUS communication only. General errors of the IQ S

ENSOR

N

ET

system are dealt with in chapter 9 W

HAT

TO

DO

IF

....

Data transmission

between the Profibus

master and

DIQ/S 182 XT-4-PR is

faulty

The PLC does not

receive any plausible

input data

Cause

Remedy

– Incorrect wiring of the

PROFIBUS cable on the
connector

– Check/change the connections

(see section 7.2)

– Use checklist according to

section 7.1

– Incorrect setting of the

address

– Check/change the setting of

the address (see section 7.3)

– Incorrect protocol

– Check the version of the GSD

file

– Adapt the protocol

– DIQ/S 182 XT-4-PR

defective

– Send DIQ/S 182 XT-4-PR to

YSI

Cause

Remedy

– Input data and output data

are not consistent

– When programming the PLC,

define input data and output
data as consistent over the
entire data length

– The data interpretation of the

PLC is not correct

– Observe the data alignment of

the PLC data representation. If
necessary, exchange the high-
order and low-order bytes word
by word