MIQ/(A-)PR

What to do if ...

29

ba76020e01

01/2012

5

What to do if ...

5.1

Fault diagnosis

A simple diagnosis of the operability of the PROFIBUS module and
communication with the PROFIBUS is possible via the LEDs on the
PROFIBUS module in the MIQ/(A-)PR (see section 3.2.4).

5.2

Error elimination

Data transmission

between the Profibus

master and

IQ S

ENSOR

N

ET

system is

faulty

The PLC does not

receive any plausible

input data

Cause

Remedy

– Incorrect wiring of the

connections on the terminal
strip

– Check/change the connections

(see section 3.2.1)

– Use checklist according to

section 3.5

– Incorrect setting of the

address

– Check/change the setting of

the address (see section 3.2.3)

– Incorrect protocol

– Check the version of the GSD

file

– Adapt the protocol

– PROFIBUS module defective

– Return the MIQ/(A-)PR to YSI

Cause

Remedy

– Input data and output data

are not consistent

– When programming the PLC,

define input data and output
data as consistent over the
entire data length

– The data interpretation of the

PLC is not correct

– Observe the data alignment of

the PLC data representation. If
necessary, exchange the high-
order and low-order bytes word
by word