YSI MIQ/Blue PS Set User Manual
Page 14
Installation
MIQ/Blue PS
3 - 4
ba76095e02
01/2013
Special features with
certain configurations
If, except in the MIQ/Blue PS, no other terminator switch is available
on the IQ S
ENSOR
N
ET
island, it must be set to ON. In addition, a ter-
minating resistor (included in the scope of delivery) must be con-
nected to one of the three SENSORNET connectors. For more
details, see page 3-6.
If a DIQ/S 182 Universal Transmitter is on the IQ S
ENSOR
N
ET
island,
all terminator switches on the IQ S
ENSOR
N
ET
island must be set to
ON.
Example of determining
the main line
The following figure shows the main line L made up of the partial
lengths L1, L2 and L3 as the cable section L4 is shorter than L3:
Length of the main line = L1 + L2 + L3
Fig. 3-2
Example of determining the length of the main line
L1
= 150 m
L4 = 200 m
L2 = 200 m
L3 = 300 m