The Hydrovar-Watercooled contains electronic safety devices which switch off the control element
in the event of a fault, whereby the motor has zero current but remains energized and comes to a

halt. The motor can also be halted by mechanical blocking. If it is electronically switched off the

motor is disconnected from the mains voltage through the electronics of the Hydrovar-Watercooled
but is not potential-free in the circuit.

In addition voltage fluctuations, especially power failures can cause the system to switch off itself.

Repair of faults can cause the motor to start up again!
The system may only be put into operation when it has been earthened. In addition, equipotential bonding of all

pipes must be ensured.

The operating instructions must be read, understood and followed by the operating personnel. We point out that we

accept no liability for damage and operating disorders which are the result of non-compliance with the operating

instructions.

Transportation, Handling:

Check the Hydrovar-Watercooled immediately upon delivery/receipt of dispatch for damage or missing parts. If
any damage is visible, inform your distributor within 8 days from the delivery date.

The unit must be transported carefully and by competent personnel.

Avoid serious impacts.

Attention: Dispose of all packing materials in accordance with local regulations

2

Technical Data

HYDROVAR Watercooled

Power supply

Max. nominal

Weight

Type

Voltage

Frequency

motor current

[kg]

HVW 1.07

0,75 kW

220-240 V +/- 15%

48-62 Hz

4,2 A

3,3


System pressure:

0 - 6 bar

Motor cable length:

max. 20 Meter

Overload:

max. 20 %

Cooling:

through handled liquid (Water, Service water)

Liquid temperature:

max. +50°C see diagram below

Ambient temperature:

0° C ... +50°C see diagram below

Storage temperature:

-25° C ... +55° C (+70°C during max. 24 hours)

Humidity:

RH max. 50% at 40°C, unlimited

RH max. 90% at 20°C, max. 30 days per year

75% average per year (Class F)

Condensation is not permitted !

Air pollution:

The air may contain dry dust as found in workshops where there is no

excessive quantity of dust due to machines.

Excessive amounts of dust, acids, corrosive gases, salts etc. are not permitted

Altitude:

max. 1000m above sea level

At sites over 1000 m above sea level, the maximum output power is derated by

1% for every additional 100m.

If the installation site is higher than 2000 m above sea level, please contact

your local distributor.

Class of protection:

IP 55

Temperature: Liquid temperature depends on the ambient temperature