Controller mode - constant pressure control:

In this mode the Hydrovar-Watercooled is controlling to a constant output pressure independent from the
required flow rate, but limited to the maximum performances of the pump. The integrated low water protection

shuts off the pump when the output pressure during operating of the pump is below 25% of the stored required

pressure for longer than 20 seconds. In that case the controller will shut off the pump and will show Error code 26

“Lack of water” (more information about Error codes you will find on page 14).

Adjustment of the required pressure:

Press (+) and (-) together for 3 seconds till all LEDs are illuminated.

The required pressure setting is now active and will be indicated by shining of LED 1 and 6. LEDs 3 and 4 in the

centre of the LED bar are blinking alternately.

1

2

3

4

5

6

Required pressure can be changed

Press (+) (=increase) or (-) (=decrease) to set the required pressure. The changing of the operating pressure of the

pump is shown on the manometer.

If no button is pressed for more than 10 seconds, the new setting will be saved automatically.

6

Error Messages

LED-Indication

Failure reason

Possible solution

Failure code 06

Under Voltage
Supply voltage is too low

Check the cable and the terminals on the

supply side of the Hydrovar

Failure code 16

Processor Error
Software failure

Check the ground and earth connection and

the cabling that no signal cable is running in

parallel with a power cable

Failure code 26

Low Water
Output pressure is below 25%

of the required pressure

The incoming water flow rate or the suction

pressure is too low

Sensor Error

Check cable connection of the internal sensor

or changing of the complete pressure

measurement device (contact your service

partner)

Failure code 36

Over-Temperature Motor/

Over-Temperature Drive
PTC of the motor has detected

over-temperature or the

Hydrovar-Watercooled has
reached its maximum

temperature.

Ambient temperature is too high or cooling of

the motor is not efficient. Clean the cover and

the motor fan and read the manual of the

motor.

Temperature of the handled liquid is too high

or no flow through the Hydrovar-Watercooled
for efficient cooling.