Assembly possibilities

Max. 45° left

Horizontal assembly

Max. 45° right

Vertical assembly

Right mounting

Possibilities for wrong mounting

WRONG –

There is no flow through

the Hydrovar-Watercooled

Inefficient cooling of the unit !

WRONG – Check valve

is mounted after the

Hydrovar-Watercooled

Wrong measuring point

for the system pressure

and therefore no

automatic stop of the

pump at zero demand.

General information about the System

The Hydrovar-Watercooled is suitable for constant pressure control of pumps and a maximum system pressure of
6 bars. The variable speed drive can be used for service water, water supply from a well or as a booster station.

The requirement for using this variable speed drive is a capable pump with an asynchronous motor suitable for a

3x230VAC supply and isolation class F.

Mounting into the pressure line with pressure tank

For applications as water supply or booster with automatic shutoff it is necessary to mount a check valve and a

pressure tank.

To measure or control the actual system pressure it is necessary that the check valve is mounted before the

Hydrovar-Watercooled.

The pressure tank can be mounted before or after the Hydrovar-Watercooled or of the not used pipe connection.

Between pressure tank and Hydrovar-Watercooled it is not allowed to mount a check valve or a pressure reduction
valve to ensure storing the pressure in the system at zero demand.

With the Hydrovar-Watercooled it is not necessary to have a large pressure tank for supply purposes.
For selecting a pressure tank, make sure it is approved and suitable for the maximum system pressure. The

pressure tank should have a capacity of more than 10% of the maximum system flow rate [l/min] of the pump.