Xylem HYDROVAR WATERCOOLED User Manual

Page 20

Advertising
background image

20

Over current /

Short circuit
Output current to te motor

is too high due to too high

nominal power of the

motor or short circuit of 2

phases of the motor or the

motor cable.

Check the power consumption of the

motor and the working point of the pump

if they do not exceed the max. output

power of the Hydrovar-Watercooled
nominal power -

Reduce the flow rate.

Check the connection to the motor.

Failure code 46

Overload
Output current is too high

Pump is blocked or tight due to solid

parts inside the pump

Failure code 56

Over voltage
Supply voltage is too high

or spikes on the supply

side.

Check the supply voltage level and all

connections -

If there are spikes on the supply line,

use special filters on the input side

After remedy of the failure reason it is necessary to switch on the Hydrovar-Watercooled.

Please contact your distributor if the same failure occurs more often. Give a detailed description of the error, the

failure code and the serial number of the Hydrovar-Watercooled.

7

Other failures and possible causes


Failure

Possible cause

Solution

Oscillation of the pressure

Wrong pre-charge pressure in the

pressure tank

Adjust pre-charge pressure

according to the required pressure

or the start pressure when active

Wrong parameter setting

Optimize control parameters

(contact customer service)

Dirty or blocked sensor

Clean the internal sensor piping

and connection

(contact customer service)

Pump does not stop

Wrong pre-charge pressure in the

pressure tank

Adjust pre-charge pressure

according to the required pressure

or the start pressure when active

Check valve is leaky or mechanically

blocked

Clean or change the check valve

Wrong parameter setting

Increase the control window setting

(contact customer service)

Air in the suction pipe or in the pump

Check the suction pipe, and

ventilate the whole system

Flexible or too long suction line

Larger pressure tank necessary

8

Maintenance and Notes

The HYDROVAR-Watercooled does not require any special maintenance!

For further information, please contact your distributor!