LEDs

are not lit. Only the Power, Status and

Remote LEDs (

,

and

) remain active

according to what described in par. 4.1.

4.3.2.2

Off

On

1. Press shortly the Up arrow button

The Numeric display

, the Parameters LEDs

and the Control mode LEDs

returns to show the

information according to the last settings before
the Off operating mode selection
2. Change the set point value with the Setting

buttons

After the transition from Off to On operating mode,
the set point (related to the actual control mode) is
equal to the minimum value: change it if
necessary.

4.3.3 Control Modes

Referring to

Figure 10

(in case of plug-connected

models) and to

Figure 11

(in case of terminal-

connected models), short press the Control mode
button

to select the desired control mode, following

this logical flow:

NOTICE
All the control modes can be combined with the Night
Mode
function (see par. 4.3.4.1)

4.3.3.1

Constant Pressure (Head)

The circulator maintains a constant pressure at any
flow demand;

for setting up the desired head of the pump (H

set

), see

par. 4.3.1.
When Constant Pressure (which is the factory setting)

is the selected control mode, the

indicator is

permanently lit
If the hydraulic working point allows the circulator to be
operated by regulating the head within the electric
power limits, then the target head will coincide with the
desired (set) head.

If the hydraulic working point requires the circulator to
be operated at a working point that exceeds the
electric power limits, then the target head will be de-
rated to remain within the maximum power limitation
curve.

4.3.3.2

Proportional Pressure (Head)

The

circulator

pressure

is

continuously

increased/decreased

depending

on

the

increased/decreased flow demand;

for setting up the desired maximum head of the pump
(H

set

), see par. 4.3.1.

When Proportional Pressure is the selected control

mode, the

indicator is permanently lit

If the hydraulic working point allows the circulator to be
operated by regulating the head within the electric
power limits, then the target head will coincide with the
desired (set) head.
If the hydraulic working point requires the circulator to
be operated at a working point that exceeds the
electric power limits, then the target head will be de-
rated to remain within the maximum power limitation
curve.

4.3.3.3

Fixed speed

The circulator maintains a fixed speed at any flow
demand;

for setting up the desired speed of the pump, see par.
4.3.1.
When Fixed Speed is the selected control mode, the

indicator is permanently lit

If the hydraulic working point allows the circulator to be
operated by regulating the speed within the electric
power limits, then the target speed will coincide with
the desired (set) speed.
If the hydraulic working point requires the circulator to
be operated at a working point that exceeds the
electric power limits, then the target speed will be de-
rated to remain within the maximum power limitation
curve.

4.3.4 Special Functions

4.3.4.1

Night Mode

The Night Mode function cannot be used in cooling
systems.

Prerequisites:

The circulator is installed in the supply line