Xylem ECOCIRC XL, XLplus Electronic drive User Manual

Page 13

Advertising
background image

5. Use the Setting buttons

, in order to select

the desired value for every parameter

6. Press the Parameter button

to confirm and

store the value selected

7. Press the Control mode button

to exit each

sub-menu, thus returning to the previous level


If no buttons are pressed for 10 seconds, then the
pump exits the current menu and continues start-up
procedure. All the parameters changed without
confirmation are restored at former state.

4.3.5.3

Differential Pressure Sensor

When an external differential pressure is connected to
the circulator, as described in par. 2.5.4, then powering
on the circulator, as described in par. 3, a submenu is
made available for setting the differential pressure
sensor’s parameter.

Referring to

Figure 10

(in case of plug-connected

models) and to

Figure 11

(in case of terminal-

connected models), the

differential pressure sensor’s

settings are accessible following the subsequent
procedure.

1. Switch on the power supply to the pump
2. After few seconds, the drive will display the

message

PrE

(

10

) or

PrES

(

11

).

3. While this message (

“PRE” or “PRES”) is

displayed, press shortly the Parameter button

in order to configure the subsequent

parameter:

Type: the message

tYP

(

10

) or

tYPE

(

11

) is displayed onto the Numeric Display

: by mean of it, the user can select a

specific differential pressure range.
Available values for this parameter are:

- [0

1bar]

dO1

(factory default)

- [0

2bar]

d02

4. Press the Parameter button

to enter each

sub-menu, thus accessing to the next level.

5. Use the Setting buttons

, in order to select

the desired value for the parameter

6. Press the Parameter button

to confirm and

store the value selected

7. Press the Control mode button

to exit each

sub-menu, thus returning to the previous level


If no buttons are pressed for 10 seconds, then the
pump exits the current menu and continues start-up
procedure. All the parameters changed without
confirmation are restored at former state.