Xylem ECOCIRC XL, XLplus Electronic drive User Manual

Page 17

Advertising
background image

o Const

ΔP/T, negative relation P/T, using

external temp. sensor

According to what described in par. 6.1.1, the
necessary correspondent settings are:

- 0x0030 - Temperature Control Mode = 1
- 0x0031

– Absolute Temperature Setpoint =

desired value

- 0x0033

– Temperature Probe = 1

- 0x0034

– Temperature Slope = 1

- Control Mode = Constant Pressure (settable

via User Interface)

- Constant Pressure Setpoint = desired value

6.1.2.4

Proportional pressure depending on
water temperature [Prop

ΔP/T]

In this control mode the drive alters the proportional
pressure set-point the pump has to maintain,
depending on the measured fluid temperature

Referring to

Figure 3

Tmin = 20

C

Tmax = Absolute Temperature Setpoint (par.
0x0031)

Hsmin = 30% of Hsmax

Hsmax = Proportional pressure set-point
(settable via User Interface, see par. 4.3.3.2)


According to what already described in par. 6.1.2.3,
even the Prop

ΔP/T control mode can be evidently

deployed in the subsequent possible application

o Prop

ΔP/T, positive relation P/T, using internal

temp. sensor

According to what described in par. 6.1.1, the
necessary correspondent settings are:

- 0x0030 - Temperature Control Mode = 1
- 0x0031

– Absolute Temperature Setpoint =

desired value

- 0x0033

– Temperature Probe = 0

- 0x0034

– Temperature Slope = 0

- Control Mode = Proportional Pressure

(settable via User Interface)

- Proportional Pressure Setpoint = desired value

o Prop

ΔP/T, negative relation P/T, using internal

temp. sensor

According to what described in par. 6.1.1, the
necessary correspondent settings are:

- 0x0030 - Temperature Control Mode = 1
- 0x0031

– Absolute Temperature Setpoint =

desired value

- 0x0033

– Temperature Probe = 0

- 0x0034

– Temperature Slope = 1

- Control Mode = Proportional Pressure

(settable via User Interface)

- Proportional Pressure Setpoint = desired value

o Prop

ΔP/T, positive relation P/T, using external

temp. sensor

According to what described in par. 6.1.1, the
necessary correspondent settings are:

- 0x0030 - Temperature Control Mode = 1
- 0x0031

– Absolute Temperature Setpoint =

desired value

- 0x0033

– Temperature Probe = 1

- 0x0034

– Temperature Slope = 0

- Control Mode = Proportional Pressure

(settable via User Interface)

- Proportional Pressure Setpoint = desired value

o Prop

ΔP/T, negative relation P/T, using external

temp. sensor

According to what described in par. 6.1.1, the
necessary correspondent settings are:

- 0x0030 - Temperature Control Mode = 1
- 0x0031

– Absolute Temperature Setpoint =

desired value

- 0x0033

– Temperature Probe = 1

- 0x0034

– Temperature Slope = 1

- Control Mode = Proportional Pressure

(settable via User Interface)

- Proportional Pressure Setpoint = desired value

6.1.3 Water Temperature dependent

Control Modes

– Circulator Control

Panel

In order to configure the desired Temperature-
dependent control mode using Circulator Control
Panel
, refer to the Advanced Tab

6.1.3.1

Advanced Tab

Collects two subset of parameters:

The subset used for advanced settings, as
described in this technical sheet at par. 8.2.1.2

The subset used for twin pump settings, as
described in this technical sheet at par. 8.2.1.3