Ar. 8.2.1.3, 8 appendix 2 – modbus registers, 1 data organization – Xylem ECOCIRC XL, XLplus Electronic drive User Manual

Page 23: 1 parameters tables, 2 information tables

Advertising
background image

8 Appendix 2

– Modbus

registers

8.1 Data Organization

The drive offers the below Modbus Virtual Memory
(see par. 8.2), based on a data set that can be divided
into 2 main subsets:

Parameters

, that is “Readable and Writable”

data [R/W] used for setting a specific
behaviour, activating a function, writing data,
etc. inside the drive.

Information, th

at is “Readable” data [R], used

for acquiring values or feedbacks from the
drive

8.2 Modbus Virtual Memory

The complete data-set managed by the ecocirc XLplus
is accessible considering a Modbus Virtual Memory
made exclusively of Holding Registers, representing
both Parameters and Information: readable and
writable the Parameters, readable only the Information.

For a detailed description of the Modbus Virtual
Memory organization, refer to the related document
“ecocircXL - Modbus Parameters Table”.

8.2.1 Parameters Tables

8.2.1.1

Parameters Table 1

It is a set of parameters [R/W] used for standard
settings
: generally the same operations or functions a
user can perform/activate through the user interface.

MB. ADDRESS

(HEX)

PARAMETER DESCRIPTION

0x0000

OPERATING MODE

0 = OFF

1 = ON

0x0001

CONTROL MODE

1 = CONSTANT PRESSURE

2 = PROPORTIONAL PRESSURE

3 = CONSTANT CURVE

0x0002

NIGHT-MODE ACTIVATION

0 = NOT ACTIVE

1 = ACTIVE

0x0003

AIR VENTING PROCEDURE

0 = NOT ACTIVE

1 = ACTIVE

0x0004

PROPORTIONAL PRESSURE SETPOINT

(for CONTROL MODE = 2)

0x0005

CONSTANT PRESSURE SETPOINT

(for CONTROL MODE = 1)

0x0006

CONSTANT CURVE SETPOINT

(for CONTROL MODE = 3)

0x0007

AIR VENTING POWER ON

0 = NOT ACTIVE

1 = ACTIVE

8.2.1.2

Parameters Table 2

It is a set of parameters [R/W] used for advanced
settings
: these operations or functions cannot be
performed/activated through the user interface

MB. ADDRESS

(HEX)

PARAMETER DESCRIPTION

0x0030

TEMPERATURE CONTROL MODE

0 = NOT ACTIVE

1 = PROP. TEMPERATURE TO HEAD

2 = CONSTANT TEMPERATURE

0x0031

ABSOLUTE TEMPERATURE SETPOINT

0x0032

DIFFERENTIAL TEMPERATURE SETPOINT

0x0033

TEMPERATURE PROBE

0 = INTERNAL

1 = EXTERNAL

2 = DIFFERENTIAL

0x0034

TEMPERATURE SLOPE

0 = INCREASING

1 = DECREASING

0x0035

K

P

FOR TEMPERATURE CONTROL

0x0036

K

I

FOR TEMPERATURE CONTROL

0x0037

TEMPERATURE CONTROL SAMPLING TIME

8.2.1.3

Parameters Table 3

It is a set of parameters [R/W] used for twin pump
settings
.

8.2.2 Information Tables

8.2.2.1

Information Table 1

It is a set of information [R] used for standard use:
generally the same data a user can acquire through
the user interface

MB. ADDRESS

(HEX)

INFORMATION DESCRIPTION

0x0200

INPUT POWER

0x0201

HEAD [H]

0x0202

FLOW [Q]

0x0203

SPEED

0x0204

WATER TEMPERATURE

MB. ADDRESS

(HEX)

PARAMETER DESCRIPTION

0x0060

CIRCULATOR CONFIGURATION

0 = TWIN MASTER

1 = TWIN SLAVE

2 = SINGLE

0x0061

TWIN PUMPS CONTROL MODE

0 = BACKUP

1 = ALTERNATE

2 = PARALLEL