2 electrical installation, 1 power supply connection, 2 i/o connection – Xylem ECOCIRC XL, XLplus Electronic drive User Manual

Page 4: 3 wiring harness

Advertising
background image

2 Electrical installation

Power Supply: 1 x 230V ±10%, 50/60Hz

Check that the power supply line is provided with:

A mains isolator switch with a contact gap of at
least 3mm

A high-sensitivity (HS) 30mA differential switch
(RCD

– Residual Current Device), suitable for

earth fault currents with DC or pulsating DC
content

(preferably

Type

B).

If an automatic circuit breaker (CB) is required,
use an automatic circuit breaker with C-type
characteristic curve.

ecocirc XL /

XLplus

Voltage

rating

Nominal

max input

current

Recommen

ded line

protection

[A]

[A]

25-80

25-100

32-80

32-100

40-80

40-100
50-100

36-45
15-75

1

230V

50/60Hz

<2

3

32-120
40-120

50-80
65-80
55-45

1

230V

50/60Hz

<3

4

50-120
65-120
65-130

1

230V

50/60Hz

<5

6

80-120

100-120

70-145

1

230V

50/60Hz

<9

10

Table 1

2.1 Power Supply connection

For plug-connected models, see

Figure 6

and follow

the subsequent steps:
1. Open the connector cover and insert the cable

inside the cable gland

2. Pull down the contact retention spring
3. Connect the cable according to the wiring diagram
4. Align the two parts of the connector
5. Push the two parts one inside the other
6. Close the connector and tight carefully the cable

gland


For terminal-connected models, see

Figure 5

and

follow the subsequent steps:
1. Open the terminal block cover removing the

screws

2. Insert the cable inside the M20 cable gland
3. Connect the cable according to the wiring diagram

(see

Figure 7

and

Figure 9

)

a. Connect the ground (earth) lead; be sure

that the ground (earth) lead is longer than
the phase leads

b. Connect the phase leads


For cable requirements and organization of wiring
harness inside the cable glands, refer to par.

2.3

Wiring harness

.

2.2 I/O connection

1. Open the terminal block removing the screws
2. Connect the appropriate cable according to the

terminal block diagram. See

Figure 8

,

Figure 9

and

the requirements of par.

2.3

and

2.4

.

2.3 Wiring harness

For plug-connected models

Plug

connector

M12 (1)

Cable Ш

2ч5mm

M12 (2)

Cable Ш

2ч5mm

Power supply

3x
0.75÷1.5
mm

2

(2P+T)

Fault signal

2x
0.75÷1.5
mm

2

- Analog 0-

10V

- External

pressure
sensor

- External

temperature
sensor

- External

start/stop

If NO fault
signal on
this cable
gland
.
Multi-wire
control
cable,
number of
wires
according
to number
of control
circuits.
Shielded if
necessary

Multi-wire
control
cable,
number of
wires
according
to number
of control
circuits.
Shielded if
necessary

Communicati
on bus

Bus cable

Table 2

For terminal-connected models

M20 Cable

Ш 5ч13mm

M16 (1)

M16 (2)

Power supply

3x
0.75÷2.5
mm

2

(2P+T)

- Power

supply

- Fault signal

5x
0.75÷1.5
mm

2

(4P+T)

Fault signal

2x
0.75÷1.5
mm

2