6 settings priority, 4 external analog input 4-20ma, 5 external temperature sensor – Xylem ECOCIRC XL, XLplus Electronic drive User Manual

Page 6: 6 communication bus (standard), 7 communication bus (optional), 8 optional wireless / rs485 module

Advertising
background image

2.5.4 External analog input 4-20mA []

The circulator can be equipped with a 4-20mA external
differential pressure sensor, connected to terminals

and



, with the purpose of increasing the precision in

operating modes involved with pressure regulation.
For setting, in the drive, the correct pressure sensor
model used, see par. 4.3.5.3.

2.5.5 External temperature sensor []

The circulator can be equipped with an external KTY83
temperature probe (1K

Ω at 25

C), connected to

terminals



and



, with the purpose of measuring an

absolute or a differential water temperature, in
temperature dependent / influenced operating modes.
For setting, in the drive, the desired temperature-
dependent control mode, see par. 6.1.2

2.5.6 Communication bus (standard)

[]

The circulator (model ecocirc XLplus only) can
communicate remotely through a built-in RS485 port,
whose characteristics are:

Interface

RS485 (TIA/EIA) optically isolated

Baud rate

4800 / 9600 (factory setting) / 14400 /
19200 / 38400 / 56000 / 57600 baud

Data
format

8 data bits, no parity, 1 stop bit

Protocol

Modbus RTU (factory setting)
Bacnet MSTP

5

Address

1

247 Modbus RTU

0

127 Bacnet MSTP

5

ID #1 factory setting


For setting, in the drive, the correct communication
parameters, see par. 4.3.5.2.

NOTICE
This communication bus, implemented on terminals



,



and



, is the only one which can be used for

connecting 2 pumps in dual pump operations (see par.
4.3.5.1)

2.5.7 Communication bus (optional)

[]

The circulator (model ecocirc XLplus only) can
communicate remotely through an optional RS485
port, available exclusively in case the optional Wireless
module or the optional RS485 module is installed;
main characteristics of this port are:

Interface

RS485 (TIA/EIA) not isolated

Baud rate

4800 / 9600 (factory setting) / 14400 /
19200 / 38400 / 56000 / 57600 baud

Data
format

8 data bits, no parity, 1 stop bit

Protocol

Modbus RTU (factory setting)
Bacnet MSTP

5

Only on ecocirc XLplus terminal-connected models

Address

1

247 Modbus RTU

0

127 Bacnet MSTP

5

ID #1 factory setting


The aim of this additional communication bus is to
offer a connection to an external BMS, or to a generic
external

device,

even

when

the

standard

communication bus (described in 2.5.6) is used for
dual pump operations (in case of a twin-head pump or
2x single-head pumps)

NOTICE
Don’t use this communication bus, implemented on
terminals



,



and



, for connecting 2 pumps in dual

pump operations

2.5.8 Optional wireless / RS485 module

[]

The drive can be equipped with

an optional Wireless module;

an optional RS485 module

Both the modules shall be plugged inside the drive
(see

Figure 12

), fixed by the provided clips and with

the cable connected to the connector  (see par. 6.2
and 6.3).

2.6 Settings priority

All the I/O signals, described in 2.5, can interact
together changing the behavior of the circulators they
are connected to: in particular, in case two or more
signals are enabled and active at the same time, the
circulator will operate according to the setting with the
highest priority.
Refer to the table below for the settings priority:

Priority

Possible settings

User

Interface

External

Start/Stop

External

0-10V

Bus signal

1

Stop

2

Regulation

3

Stop

4

Regulation

5

Stop

6

Regulation

7

Stop


EXAMPLE 1
In case the external start/stop switch is open or
unconnected (External Start/Stop = Stop), the drive
shall not accept any regulation.


EXAMPLE 2
The circulator can be driven through the User Interface
only if no external signals are applied (to the provided
terminals) and no communication bus is connected



Advertising